User Manual

5.14 WATLOW Series 998 User’s Manual
Operation Menus, Chapter 5
Operation-PID B
PID B Prompts
After you step past the Set Point 2A prompt [SP2A] and the Set Point 2B
prompt [SP2b] to the Operation menus, the Series 998 displays the menu
selection ( [`SYS], [PidA] or [PidB] ) in the upper display and [OPEr] in
the lower display.
The Up-arrow > or Down-arrow key < selects another menu. Press the
Mode key µ to display the first prompt in the lower display and its value
in the upper display. Use the Up-arrow and Down-arrow keys to change
the value in the upper display. The new value will not take effect until
after a five-second delay or until you press the Mode key.
Proportional Band, Output 1B or 2B
Select the proportional band for PID channel A outputs. If set to
[```0] it functions as an on/off control, and the switching differential is
determined by the [HY1b] or [Hy2b] value (Output Menu). The decimal
precision is determined by [dEC1] (Input Menu).
[Pb1b] This prompt always appears.
If Default
↓↓
[``US]
&
process
[```0]
[``25]
[`999]
[`dFL] [`In2] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu)(Global Menu)
[``US]
&
[``°F] [```0]
[``25]
[`999]
[`dFL] [`C_F] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu)(Global Menu)
the above
&
[`r†d] [``)0]
[``25]
[99(9]
[`In2] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu) (Input Menu)
[``US]
&
[``°C] [```0]
[``14]
[`555]
[`dFL] [`C_F] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu)(Global Menu)
the above
&
[`r†d] [``)0]
[`1$0]
[55%5]
[`In2] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu) (Input Menu)
[``SI] [``)0]
[``#0]
[`9(9]
% of span
[`dFL] [Pb1b] [Pb1b] [Pb1b]
(Calibration Menu)
[Pb1B]
[Pb2b]
NOTE:
Decimal points may
not always be in the
position specified
below depending
on the the settings
in the Decimal 1
[dEC1] parameter
in the Input Menu.