User Manual

4.40 WATLOW Series 998 User’s Manual
Setup Menus, Chapter 4
Setup-Communications
Protocol Type
Select the communications protocol.
[FULL] selects ANSI X3.28 2.2 - A.3.
[``on] selects XON/XOFF.
[Prot] This prompt appears only on controllers equipped with communi-
cations hardware (99__-____-_R__ or 99__-____-_S__).
Default
[FULL] [``On]
[Prot] [Prot]
Address
Select an address for the controller. The computer will use this address
when communicating with this controller.
[Addr] This prompt appears only on controllers equipped with communica-
tions hardware for EIA/TIA-485 and EIA/TIA-422 (99__-____-_S__).
If Default
↓↓
[`485] [```0] [``31]
[IntF] [Addr] [Addr]
[`422] [```0] [```9]
[Intf] [Addr] [Addr]
Interface Type
Select the interface type.
[`485] selects EIA/TIA-485.
[`422] selects EIA/TIA-422.
[IntF] This prompt appears only on controllers equipped with communi-
cations hardware for EIA/TIA-485 and EIA/TIA-422 (99__-____-_S__).
Default
[`485] [`422]
[IntF] [IntF]
[Addr]
[IntF]
[Prot]