User Manual

4.30 WATLOW Series 998 User’s Manual
Setup Menus, Chapter 4
Process 3
Select the range for the retransmit signal at output 3.
[Prc3] This prompt appears only on controllers equipped with output 3
retransmit hardware (99__-____-M___ or 99__-____-N___) and with [Aout]
not set to [``no].
Default
4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[Prc3] [Prc3] [Prc3] [Prc3] [Prc3]
Retransmit Low Limit
Select the low limit for the retransmit signal at output 3.
• The default value is equal to [`rL1] or [`rL2] (in the Input Menu)
depending on whether [Aout] is set to [PrcA] or [Prcb].
[`ArL] This prompt appears only on controllers equipped with retransmit
hardware (99__-____-M___ or 99__-____-N___) and with [Aout] not set to
[``no].
[-999] [`ArH]
[`ArL] [`ArL]
Setup-Output
[Prc3]
[`ArL]
NOTE:
See Chapter 8 for
more information on