User Manual

WATLOW Series 998 User’s Manual 4.13
Setup Menus, Chapter 4
Calibration Offset 2
Offset the channel B signal by a positive or negative value. This allows
you to compensate for lead resistance, sensor errors or other factors.
[CAL2] This prompt appears only if [`In2] is not set to [``no].
If Default
↓↓
[``°F] [-999] [```0] [`999]
[`C_F] [CAL2] [CAL2] [CAL2]
(Global Menu)
[``°F]
&
[`r†d] [-9(9] [``)0] [`9(9]
[`C_F] [`In2] [CAL2] [CAL2] [CAL2]
(Global Menu) (Input Menu)
[``°C] [-555] [```0] [`555]
[`C_F] [CAL2] [CAL2] [CAL2]
(Global Menu)
[``°C]
&
[`r†d] [-5%5] [``)0] [`5%5]
[`C_F] [`In2] [CAL2] [CAL2] [CAL2]
(Global Menu) (Input Menu)
[-999] [```0] [`999]
units
a process input
[CAL2] [CAL2] [CAL2]
is selected
RTD Calibration Curve 2
Select the calibration curve for the channel B RTD 2 input. The RTD
input uses either the European (DIN, 0.003850//°C) or the Japanese
(JIS, 0.003916//°C) linearization standard.
[rtd2] This prompt appears only if you have set [`In2] to [`rtd] or
[`r†d].
Default
[`din] [`JIS]
[rtd2] [rtd2]
Setup-Input
[CAL2]
[rtd2]