Temperature/process Controller Prompt Table
986, 987,
988, 989
Name Description Read (?) and/or Write (=) Syntax Range
data.1 data.2
Modbus
address
6.6
Command Summary Series 986-989, Chapter 6
FTR1 Process Input 1 ? <sp> FTR1 <cr> -60 to 60 seconds
53 Filter Time Constant = <sp> FTR1 <sp> data.2 <cr> Default: 0
FTR2 Process Input 2 ? <sp> FTR2 <cr> -60 to 60 seconds
63 Filter Time Constant = <sp> FTR2 <sp> data.2 <cr> Default: 0
GLBL Lockout ? <sp> GLBL <cr> 0 = No lockout
118 Global Menu = <sp> GLBL <sp> data.2 <cr> 1 = Read only
2 = No read or write
Default: 0
HIP High Power Limit ? <sp> HIP <cr> LOP (%) to 100%
108 = <sp> HIP <sp> data.2 <cr> Default: 100 (Heat / cool)
Default: 0 (Cool only)
HUNT Slidewire ? <sp> HUNT <cr> 0.1% to 100.0%
65 Deadband % = <sp> HUNT <sp> data.2 <cr> Default: 1.0%
HYS1 Output 1 Hysteresis ? <sp> HYS1 <cr> 0°F to 999°F
69 = <sp> HYS1 <sp> data.2 <cr> 0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units
HYS2 Output 2 Hysteresis ? <sp> HYS2 <cr> 0°F to 999°F
72 = <sp> HYS2 <sp> data.2 <cr> 0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units
HYS3 Output 3 Hysteresis ? <sp> HYS3 <cr> 0°F to 999°F
81 = <sp> HYS3 <sp> data.2 <cr> 0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units
IDSP Idle Set Point ? <sp> IDSP <cr> RL1 to RH1
9 = <sp> IDSP <sp> data.2 <cr>
IN1 Input 1 Type ? <sp> IN1 <cr> 1 = J t/c; 32 to 1500°F/0 to 816°C
47 = <sp> IN1 <sp> data.2 <cr> 2 = K t/c; -328 to 2500°F/-200 to 1371°C
(Caution: Writing to 3 = T t/c; -328 to 750°F/-200 to 399°C
IN1 resets most 4 = N t/c; 32 to 2372°F/0 to 1300°C
prompts to their de- 5 = E t/c; -328 to 1470°F/-200 to 799°C
fault state.) 6 = C t/c (W3); 32 to 4200°F 0 to 2316°C
7 = D t/c (W5); 32 to 4200°F/0 to 2316°C
8 = Pt 2; 32 to 2543°F/0 to 1395°C
10 = R t/c; 32 to 3200°F/0 to 1760°C
11 = S t/c; 32 to 3200°F/0 to 1760°C
12 = B t/c; 1598 to 3300°F/870 to 1816°C
14 = 1° RTD (DIN); -328 to 1472°F/
-200 to 800°C
15 = 0.1° RTD (DIN); -99.9 to 999.9°F/
-99.9 to 700.0°C
17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5VÎ (dc); -999 to 9999 units
20 = 1-5VÎ (dc); -999 to 9999 units
21 = 0-10VÎ (dc); -999 to 9999 units
23 = 0-50mVÎ (dc); -999 to 9999 units
24 = 0-100mVÎ (dc); -999 to 9999 units
34 = 0-50mVÎ (dc); -999 to 9999 units
Table 6.6 -
FTR1 to IN1
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 986-989
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
NOTE:
The number of
decimal places
returned by many
of these
commands is
determined by the
DEC1, DEC2, IN1
or IN2 setting.
NOTE:
(RTD setting)
For JIS curve, go
to rtd1 prompt
after selecting In1.