User guide

Ramping Controller Commands
NOTE:
"*" means the
parameter is
not available.
The value will
be -9999.
MTR response for a Set Point Step, Time-based(PTYP = TI)
Register # 1200 1201 1202 1203 1204 1205 1206 1207 1208 1209 1210
Parameter File Step Type SP Hour Min Sec ****
MTR response for a Set Point Step, Rate-based(PTYP = RATE)
Register # 1200 1201 1202 1203 1204 1205 1206 1207 1208 1209 1210
Parameter File Step Type SP * * * Rate * * *
MTR response for a Soak Step
Register # 1200 1201 1202 1203 1204 1205 1206 1207 1208 1209 1210
Parameter File Step Type * Hour Min Sec ****
PROGRAM command for a Set Point Step, Time-based(PTYP = TI)
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type SP Hour Min Sec * * *
PROGRAM command for a Set Point Step, Rate-based(PTYP = RATE)
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type SP * * * Rate JF *
PROGRAM command for a Soak Step
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type * Hour Min Sec * * *
PROGRAM command for a Jump Loop Step
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type *****JFJS
PROGRAM command for a Link File Step
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type *******
PROGRAM command for an End Step Step
Register # 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260
Parameter 2 File Step Type *******
MONITOR (MTR) Command
READ only
Register: 1200 (You must request 23 registers)
START (STRT) Command
WRITE only
Register: 1250 1251 1252
Value: 1 File # Step #
SET command, sets the current profile FILE and STEP.
WRITE only
Register: 1250 1251 1252
Value: 3 File # Step #
STEP (STP) Command
READ the current file and step
Register: 1201 (You must request 23 registers)
Response will be the same as the PROGRAM commands below,
(1201 = 1251, 1202 = 1252 etc.)
WRITE (program) the specified file and step.
(You must send a "*" (-9999) if a register is disabled or unavailable)
NOTE:
"*" means the
parameter is
not available.
The value will
be -9999.
981,
982, 983, 984
5.14