User guide

Name Description Read (?) and/or Write (=) Syntax Range
data.1 data.2
Modbus
Address
Ramping Controller Prompt Table
981, 982,
983, 984
Command Summary Series 981-984, Chapter 5 Data Communications with the Watlow Series 988 Family
5.9
OTY1 Output 1 Hardware ? <sp> <OTY1> <cr> 0 = None
16
OTY2 Output 2 Hardware ? <sp> <OTY2> <cr> 1 = SSR 0.5A
17
OTY3 Output 3 Hardware ? <sp> <OTY3> <cr> 2 = SSR 0.5A with suppression
18
OTY4 Output 4 Hardware ? <sp> <OTY4> <cr> 5 = Dual SSR form A
19 6 = Switched dc
7 = Dual switched dc
8 = Relay 5A form C
9 = Relay 5A form C with suppression
10 = Relay 5A form A/B
11 = Relay 5A form A/B with suppr.
12 = Dual Relay form A
13 = Process output
14 = Voltage retransmit
15 = Current retransmit
16 = Power supply
17 = Comms EIA-232
18 = Comms EIA-485 / EIA-422
19 = Comms EIA-485 / EIA-232
PB1 Proportional Band ? <sp> PB1 <cr> if DFL = 0 and CF = 1, then 0 to 555°C
500 Output 1 = <sp> PB1 <sp> data.2 <cr> if DFL = 0 and CF = 0, then 0 to 999°F
if DFL = 0 and In1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%
PB2 Proportional Band ? <sp> PB2 <cr> if DFL = 0 and CF = 1, then 0 to 555°C
510 Output 2 = <sp> PB2 <sp> data.2 <cr> if DFL = 0 and CF = 0, then 0 to 999°F
if DFL = 0 and In1 = a process value,
then 0 to 999 units
if DFL = 1, then 0.0 to 99.9% of span
Default: 25°F, 14°C, 25 units, or 3.0%
POUT Power Outage ? <sp> POUT <cr> 0 = Continue
1206 Response = <sp> POUT <sp> data.2 <cr> 1 = Hold (HOLD)
2 = Abort
3 = Idle set point (IDSP)
4 = Reset
PRC1 Process Range ? <sp> PRC1 <cr> 0 = 4-20mA
701 Output 1 = <sp> PRC1 <sp> data.2 <cr> 1 = 0-20mA
2 = 0-5V
3 = 1-5VÎ (dc)
4 = 0-10VÎ (dc)
Default: 0
PRC2 Process Range ? <sp> PRC2 <cr> 0 = 4-20mA
718 Output 2 = <sp> PRC2 <sp> data.2 <cr> 1 = 0-20mA
2 = 0-5VÎ (dc)
3 = 1-5VÎ (dc)
4 = 0-10VÎ (dc)
Default: 0
PRC3 Process Range ? <sp> PRC3 <cr> 0 = 4-20mA
735 Output 3 = <sp> PRC3 <sp> data.2 <cr> 1 = 0-20mA
2 = 0-5VÎ (dc)
3 = 1-5VÎ (dc)
4 = 0-10VÎ (dc)
Default: 0
PSTR Program Start Point ? <sp> PSTR <cr> 0 = Start @ current process value
1207 = <sp> PSTR <sp> data.2 <cr> 1 = Start @ hold mode set point
Default: 1
Table 5.9 -
OTY1 to PSTR
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)