User guide

Name Description Read (?) and/or Write (=) Syntax Range
data.1 data.2
Modbus
Address
Ramping Controller Prompt Table
981, 982,
983, 984
Data Communications with the Watlow Series 988 Family Command Summary Series 981-984, Chapter 5
5.6
ER2 Error, ? <sp> ER2 <cr> 0 = No error
n/a Communications 1 = Transmit buffer overflow
2 = Receive buffer overflow
3 = Framing error
4 = Overrun error
5 = Parity error
6 = Talking out of turn
7 = Invalid reply error
8 = Noise error
20 = Command not found
21 = Prompt not found
22 = Incomplete command line
23 = Invalid character
24 = Number of chars. overflow
25 = Input out of limit
26 = Read only command
27 = Write allowed only
28 = Prompt not active
30 = Request to RUN invalid
31 = Request to HOLD invalid
32 = Command invalid in RUN Mode
33 = Command invalid in HOLD Mode
34 = Output 3 is not an Event
35 = Output 4 is not an Event
38 = Asterisk not allowed
39 = Infinite loop error
ERR Error, ? <sp> ERR <cr> 0 = Errors latching
607 Latching Enable = <sp> ERR <sp> data.2 <cr> 1 = Errors non-latching
Default: 1
FTR1 Filter Time Constant ? <sp> FTR1 <cr> -60 to 60 seconds
604 Process Input 1 = <sp> FTR1 <sp> data.2 <cr> Default: 0
GSD Guaranteed Soak ? <sp> GSD <cr> 0°F to 999°F
1205 Deviation = <sp> GSD <sp> data.2 <cr> 0°C to 999°C
0 to 999 units
0 = (disabled)
Default: 0°F, 0°C, or 0 units
HIP High Power Limit ? <sp> HIP <cr> LOP (%) to 100%
714 = <sp> HIP <sp> data.2 <cr> Default: 100 (heat/cool)
Default: 0 (cool only)
HOLD Simulate HOLD = <sp> HOLD <sp> data.2 <cr> 1 = Holds current file# and step#
1210 Key Press
HUNT Slidewire ? <sp> HUNT <cr> 0.1% to 100.0%
1905 Dead Band % = <sp> HUNT <sp> data.2 <cr> Default: 1.0%
HYS1 Output 1 Hysteresis ? <sp> HYS1 <cr> 0°F to 999°F
507 = <sp> HYS1 <sp> data.2 <cr> 0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units
HYS2 Output 2 Hysteresis ? <sp> HYS2 <cr> 0°F to 999°F
517 = <sp> HYS2 <sp> data.2 <cr> 0°C to 555°C
720 0 units to 999 units
Default: 3°F, 2°C, or 3 units
HYS3 Output 3 Hysteresis ? <sp> HYS3 <cr> 0°F to 999°F
737 = <sp> HYS3 <sp> data.2 <cr> 0°C to 555°C
0 units to 999 units
Default: 3°F, 2°C, or 3 units
Table 5.6 -
ER2 to HYS3
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)