Name Description Read (?) and/or Write (=) Syntax Range
data.1 data.2
Modbus
Address
Ramping Controller Prompt Table
981, 982,
983, 984
Data Communications with the Watlow Series 988 Family Command Summary Series 981-984, Chapter 5
5.4
ANUN Alarm Annunciation ? <sp> ANUN <cr> 0 = off
725 = <sp> ANUN <sp> data.2 <cr> 1 = on
Default: on
AOUT Analog Output 3 ? <sp> AOUT <cr> 0 = Retransmit Process Input 1
743 Retransmit Function = <sp> AOUT <sp> data.2 <cr> 1 = Retransmit Set Point 1
2 = off
3 = Retransmit Process Input 2
Default: 0
ARH Retransmit ? <sp> ARH <cr> ARL to 9999
745 Range High = <sp> ARH <sp> data.2 <cr> Default: RH1 or RH2 per AOUT
ARL Retransmit ? <sp> ARL <cr> -999 to ARH
744 Range Low = <sp> ARL <sp> data.2 <cr> Default: RL1 or RL2 per AOUT
ATSP Auto-tune ? <sp> ATSP <cr> 50 to 150%
304 Set Point % = <sp> ATSP <sp> data.2 <cr> Default: 90%
AUT Auto-tune ? <sp> AUT <cr> 0 = No auto-tuning
305 = <sp> AUT <sp> data.2 <cr> 1 = Tune PID
Default: off
C1 Input 1 Value ? <sp> C1 <cr> Based on IN1 range ; RL1 to RH1
100
C2 Input 2 Value ? <sp> C2 <cr> Based on IN2 range ; RL2 to RH2
104
CAL1 Input 1 Calibration ? <sp> CAL1 <cr> -999°F to 999°F
605 Offset = <sp> CAL1 <sp> data.2 <cr> -555°C to 555°C
-999 units to 999 units
Default: 0
CAL2 Input 2 Calibration ? <sp> CAL2 <cr> -999°F to 999°F
615 Offset = <sp> CAL2 <sp> data.2 <cr> -555°C to 555°C
-999 units to 999 units
Default: 0
CF Degrees Select ? <sp> CF <cr> 0 = Display °F
901 Display Loop = <sp> CF <sp> data.2 <cr> 1 = Display °C
Default: 0
CSP Current Profile ? <sp> CSP <cr> RL1 to RH1
1202 Set Point
CT1 Cycle Time ? <sp> CT1 <cr> S.S. relay or open col:
506 Output 1 = <sp> CT1 <sp> data.2 <cr> 0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.
CT2 Cycle Time ? <sp> CT2 <cr> S.S. relay or open col:
516 Output 2 = <sp> CT2 <sp> data.2 <cr> 0.0 = Burst firing, or
0.1 to 999.9 sec. (time prop)
Mech relay: 5.0 to 999.9 sec.
Default: 1.0 or 10.0 sec.
DATE Factory Test Date ? <sp> DATE <cr> xxyy
5 xx = week
yy = year
DB Dead Band PID ? <sp> DB <cr> -999°F to 999°F
505 Heat/Cool = <sp> DB <sp> data.2 <cr> -555°C to 555°C
-999 units to 999 units
Default: 0°F, 0°C, or 0 units
DE1 Derivative ? <sp> DE1 <cr> 0.00 to 9.99 minutes
503 Output 1 PID = <sp> DE1 <sp> data.2 <cr> Default: 0.00
Table 5.4 -
ANUN to DE1
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.
(This does not
apply to Modbus
Protocol.)