User guide

A.12 Appendix Watlow Series 97
Thermocouple Input Procedure
Equipment
Type J reference compensator with reference junction at 32°F/0°C, or type J
thermocouple calibrator to 32°F/0°C.
• Precision millivolt source, 0 to 50mV minimum range, 0.002mV resolution.
Input 1 Setup and Calibration
1. Connect the correct power supply to terminals 8 and 9 (see Chapter Three
and the Appendix).
2. Connect the millivolt source to terminals 6 (-) and 7 (+) with copper wire.
3. Enter 50.000mV from the millivolt source. Allow at least 10 seconds to
stabilize. Set Thermocouple Calibration, 50mV [tc50] (Input Calibration
Menu) to [`yES]. Press the Advance Key to store 50.000mV input and
move to the next prompt.
4. Enter 0.000mV from the millivolt source. Allow at least 10 seconds to
stabilize. Set Thermocouple Calibration, 0mV [tc00] (Input Calibration
Menu) to [`yES]. Press the Advance Key to store 0.000mV input and
move to the next prompt.
5. Disconnect the millivolt source and connect the reference compensator or
thermocouple calibrator to terminals 6 (-) and 7 (+). With type J
thermocouple wire, if using a compensator, turn it on and short the input
wires. When using a type J calibrator, set it to simulate 32°F/0°C. Allow 10
seconds for the controller to stabilize. Set Thermocouple Calibration, 32°
[tc32] (Input Calibration Menu) to [`yES]. Press the Advance Key to
store type J thermocouple calibration and move to the next prompt.
6. Rewire for operation and verify calibration.
RTD Input Procedure
Equipment Required
• 1k decade box with 0.01 resolution.
Input 1 Setup and Calibration
1. Connect the correct power supply to terminals 8 and 9 (see Chapter Three
and the Appendix).
2. Short terminals 5, 6 and 7 together with less than 0.1. Set Ground [`gnd]
(Input Calibration Menu) to [`yES]. Press the Advance Key to store
ground input and move to the next prompt.
2. Short terminals 5 and 7 together with less than 0.5. Set Lead Resistance
Calibration [LEAd] (Input Calibration Menu) to [`yES]. Press the Advance
Key to store the lead resistance and move to the next prompt.
4. Connect the decade box to terminals 5 (S2), 6 (S3) and 7 (S1), with 20- to 24-
gauge wire.
5. Enter 15.00 from the decade box. Allow at least 10 seconds to stabilize. Set
RTD Calibration, 15 [r`15] (Input Calibration Menu) to [`yES]. Press
the Advance Key to store the 15.00 input and move to the next prompt.
6. Enter 380.00 from the decade box. Allow at least 10 seconds to stabilize.