User guide

Watlow Series 97 Features 5.7
Retransmit
The retransmit output can be used to transmit an analog signal representing the value of
the input process variable. The retransmit signal can be configured as either a milliamp or
a voltage signal. In choosing the type of retransmit signal the operator must take into
account the input impedance of the external device and the required signal type, either volt-
age or milliamps.
A typical application might use the retransmit option to record a process value with a chart
recorder.
Figure 5.7 — Retransmit example.
In the example a Series 96 is being used to control the temperature of a heat-treat oven and
the Series 97 is being used as a safety limit with a retransmit output. Output 4 of the
Series 97 must be equipped for retransmit (97_ _ - _ _ _ M - _ _ _ _).
The temperature of the limit process value is being recorded on a chart recorder. The oven
temperature range stays between 600 to 900°F. The chart recorder requires a 4-20mA sig-
nal.
Set [Aout] Analog Output 4 (Output 4 Menu) to [Proc] Process 1 and [Prc4] Process 4
(Output 4 Menu) to [4-20] to tag the input 1 process value as the parameter to be retrans-
mitted. Set Analog Output High [A`hi] to 900 to set the high range for the retransmit sig-
nal. Set Analog Output Low [A`Lo] to 600 to set the low range for the retransmit signal.
Set Analog Output Offset [ACAL] to 0, assuming no calibration offset is required.
The retransmit output will be 4mA until the oven temperature is greater than 600°F, at
which point the signal will increase with temperature to 20mA at 900°F and will not exceed
20mA.
Temperature Controller
Limit Controller
input 1 output 1
heater
234 %
96
1
234
LIMIT 97
1
RESET
input 1
output 1
output 4
Chart Recorder
Heat-treat Oven
limit
sensor
temperature
sensor
input 2