Manual

Watlow Series 96 Appendix A.6
Communications
EIA/TIA-485 or EIA/TIA-232
Opto-isolated
Modbus
TM
RTU protocol
1200, 2400, 4800, 9600, 19200 baud rates
32 maximum units can be connected (with additional 485
repeater hardware, up to 247 units may be connected)
Accuracy
Input ranges
Type J: 32 to 1382°F or 0 to 750°C
Type K: -328 to 2282°F or -200 to 1250°C
Type T: -328 to 662°F or -200 to 350°C
Type N: 32 to 2282°F or 0 to 1250°C
Type E: -328 to 1470°F or -200 to 900°C
Type C(W5): 32 to 4200°F or 0 to 2315°C
Type D(W3): 32 to 4200°F or 0 to 2315°C
Type PTII: 32 to 2540°F or 0 to 1393°C
Type R: 32 to 2642°F or 0 to 1450°C
Type S: 32 to 2642°F or 0 to 1450°C
Type B: 1598 to 3092°F or 870 to 1700°C
DIN: -328 to 1472°F or -200 to 800°C
JIS: -328 to 1166°F or -200 to 630°C
Process: -1999 to 9999 units
Thermocouple Inputs
Calibration accuracy ±0.1% of span ±1°C at standard
conditions
Exceptions:
Type T; 0.12% of span for -200°C to -50°C,
Types R and S; 0.15% of span for 0°C to 100°C
Types B; 0.24% of span for 870°C to 1700°C
Accuracy span: 1,000°F/540°C minimum
Temperature stability: ±0.1 degree per degree change in
ambient
RTD Inputs
Calibration accuracy ±0.1% of span ±1°C at standard
conditions
Accuracy span: 1,000°F/540°C minimum
Temperature stability: ±0.05 degree per degree change in
ambient
Process Inputs
Voltage input ranges
Accuracy ±10mV ±1 LSD at standard conditions
Temperature stability ±100ppm/°C maximum
Milliamp input ranges
Accuracy ±20µA ±1 LSD at standard conditions
Temperature stability ±100ppm/°C maximum
Agency Approvals
UL 916 Listed file Number E185611; c-UL Approved,
UL CCN QQXY, QQXY7 Process Control Equipment
CE and NEMA 4X approved.
Modbus™ is a trademark of AEG Schneider Automation.
UL
®
is a registered trademark of the Underwriter’s Laboratories, Inc.
Terminals
Touch safe
22 to 12 AWG
Power
100-240V (ac/dc) +10%; -15%; 50/60Hz, ±5%
24-28V (ac/dc) +10%; -15%; 50/60Hz, ±5%
7.0VA maximum power consumption
Data retention upon power failure via nonvolatile memory
Operating Environment
32 to 149°F, 0 to 65°C
0 to 90% RH, non-condensing
Storage temperature: -40 to 185°F, -40 to 85°C
Dimensions
Width 2.05 in. or 52mm
Height 2.05 in. or 52mm
Length 4.2 in. or 107mm
Depth behind panel surface 3.875 in. or 98.4mm
Approximate controller weight 0.4 lbs (0.2 kg)
Allowable Operating Ranges
Type J: 1.0 32 to 1,500°F or 0 to 815°C
0.1 32.0 to 999.9°F or 0.0 to 815.0°C
Type K: 1.0 -454 to 2,500°F or -270 to 1,370°C
0.1 -199.9 to 999.9°F or -199.9 to 999.9°C
Type T: 1.0 -454 to 750°F or -270 to 400°C
0.1 -199.9 to 750.0°F or -199.9 to 400.0°C
Type N: 1.0 32 to 2,372°F or 0 to 1,300°C
0.1 32.0 to 999.9°F or 0.0 to 999.9°C
Type E: 1.0 -454 to 1,470°F or -270 to 800°C
0.1 -199.9 to 999.9°F or -199.9 to 800.0°C
Type C: 1.0 32 to 4,200°F or 0 to 2,315°C
0.1 32.0 to 999.9°F or 0.0 to 999.9°C
Type D: 1.0 32 to 4,200°F or 0 to 2,315°C
0.1 32.0 to 999.9°F or 0.0 to 999.9°C
Type PTII: 1.0 32 to 2,543°F or 0 to 1,395°C
0.1 32.0 to 999.9°F or 0.0 to 999.9°C
Type R: 1.0 32 to 3,200°F or 0 to 1,760°C
Type S: 1.0 32 to 3,200°F or 0 to 1,760°C
Type B: 1.0 32 to 3,300°F or 0 to 1,816°C
RTD (DIN)1.0 -328 to 1,472°F or -200 to 800°C
0.1 -199.9 to 999.9°F or -199.9 to 800.0°C
RTD (JIS) 1.0 -328 to 1,166°F or -200 to 630°C
0.1 -199.9 to 999.9°F or -199.9 to 630.0°C
Process -1,999 to 9,999 units
Note: These specifications are subject to change without prior notice.
Event &
Universal Remote 232/485
Input Set Point Control Alarm Retransmit Comm
Input 1
Input 2
Output 1
Output 2
Output 3
Output 4
Functionality Matrix