Manual

0 Model Number
1 Serial Number 1
2 Serial Number 2
3 Software ID Number
4 Software Revision
5 Date of Manufacture
9 Input 2 Hardware Enabled
16 Output 1 Hardware
17 Output 2 Hardware
18 Output 3 Hardware
19 Output 4 Hardware
24 Disable Nonvolatile Memory
100 Process 1
101 Error 1
103 Percent Output
104 Actual 2
105 Process 2
106 Alarm 2 Status
110 Alarm 3 Status
200 Operation Mode
201 Event Input Status
202 Remote Set Point
203 Ramping Set Point
204 PID Power
205 Prop Term
206 Integral Term
207 Derivative Term
209 System Error
210 Open Loop Error
300 Set Point 1
301 Auto-Manual Operation Mode
304 Auto-tune Set Point 1
305 Auto-tune Start 1
306 Event Set Point 1
310 Manual Set Point
311 Clear Input Errors
316 Local-Remote (L-r)
319 Set Point 2
321 Alarm 2 Low
322 Alarm 2 High
331 Clear Alarms
332 Silence Alarms
340 Alarm 3 Low
341 Alarm 3 High
500 Propband 1
501 Integral 1
502 Reset 1
503 Derivative 1
504 Rate 1
505 Dead Band 1
506 Cycle Time 1
507 Hysteresis 1
509 Burst 1
510 Propband 2
511 Integral 2
512 Reset 2
513 Derivative 2
514 Rate 2
515 Dead Band 2
517 Hysteresis 2
519 Burst 2
600 Sensor Type 1
601 Input 1
602 Range Low 1
603 Range High 1
604 Input Software Filter 1
605 Calibration Offset 1
606 Decimal 1
607 Input Error Latching
611 Input 2
612 Range Low 2
613 Range High 2
615 Calibration Offset 2
700 Output 1
701 Process 1 Type
713 Power Limit Set Point
714 High Power Limit Above
715 High Power Limit Below
717 Output 2
718 Process 2 Type
719 Alarm 2 Type
720 Alarm Hysteresis 2
721 Latching 2
722 Silencing 2
723 Alarm Active Sides 2
724 Alarm Logic 2
725 Alarm Annunciation 2
734 Output 3
736 Alarm 3 Type
737 Alarm Hysteresis 3
738 Latching 3
739 Silencing 3
740 Alarm Active Sides 3
741 Alarm Logic 3
742 Alarm Annunciation 3
900 Units Type
901 °C or °F
902 Failure Mode
903 Manual Default Power
904 Open Loop Detect
1060 Event Function
1061 Event Condition
1100 Ramping Mode
1101 Ramp Rate
1102 Ramp Scale
1208 Program Type
1211 Abort Set Point
1300 Set Point Menu Lock
1301 Operations Page Mode Lock
1302 Setup Page Lock
1304 Custom Menu Lock
1305 Calibration Menu Lock
1314 Program Menu Lock
1400-1415 Custom Prompt Number (1-16)
1500 Ambient Temperature
1501 Ambient A-D Counts
1504 Channel 1 A-D Counts
1505 Channel 2 A-D Counts
1513 Test Display
1514 Test Output
1515 Line Frequency
1601 Restore Factory Calibration
1602 Default Settings
A.3 Appendix Watlow Series 96
Series 96 Modbus Register Numbers
Relative Parameters Relative Parameters
Relative Parameters
Note: For Absolute Modbus numbers, add 40001 to the Relative number.
Note: Refer to p. 7.7 for Modbus Register Numbers for ramping parameters.
Special Modbus Functions
The following are modbus registers with special functions. Disable Non-volatile Memory (24); Alarm Status
Output 2 (106); Alarm Status Output 3 (110); Auto-Manual Operation Mode (200); Clear Input Errors (311);
Clear Alarms (331); Silence Alarms (332).
A “0” indicates an active state. Send “1” to the register to activate the function. It will automatically reset
to “0” when the function is complete.