Manual

A.1 Appendix Watlow Series 96
Appendix
A
Troubleshooting Alarms and Errors
• Check comms setup menu and set to correct
address.
• Check comms setup menu and set to correct
baud rate.
• Look for a break in the daisy chain.
• Verify correct connections and test wiring
paths.
• Check converter box wiring and its
documentation.
• Reconfigure computer's COM port setup and
verify communications ok.
• Check the communication card documentation
for setable variables and operational testing.
• Restart COMS software and check for settings
agreement. Verify the COM bus is active.
• Verify operation with Watlow comms tool.
• Add termination resistors per EIA-485
standards if using this option.
• Address parameter may be incorrectly set.
• Baud rate parameter may be incorrectly set.
• Unit-to-unit daisy chain may be disconnected.
• Communications wiring may be reversed,
shorted or open.
• EIA-485 converter box may be incorrectly
wired.
• Computer COM port may be incorrectly set
up.
• Communications software setup or address
may be incorrect.
• Protocol or parity may be wrong, should be 8,
n, 1.
• Application software not working properly.
• May need termination and pull-up and pull-
down resistors.
Communications
• Unit will not
communicate.
Check switches, fuses, breakers, interlocks,
limits, connectors, etc. for energized condition
and proper connection.
Measure power upstream for required level.
Check part number for input power required.
Check wire size.
Check for bad connections.
• Power to unit may be off.
• Fuse may be blown.
• Breaker may be tripped.
• Safety interlock door switch etc. may be
activated.
• Separate system limit control may be latched.
• Wiring may be open.
• Input Power may be incorrect.
Power
• No power.
Corrective ActionProbable Cause(s)Indication