Manual

Added if ramping version of the
controller is selected
(96__-____-AA__).
1208 r/w
[``ti] (0)[``ti] time based (0)
[rate] rate based (1)
[ptyp] Program Type*
Select whether the
program type will be
time based or rate
based.
Appears if Setup Page Lock
(Lockout Menu) is not set to
[hide].
904 r/w
[`OFF] (0)[`OFF] off (0)
[``on] on (1)
[OPLP] Open Loop
Detect
Turn the open loop
detect feature on or
off.
Active if Local or Remote Mode
(User Menu) is not set to
[```r] , Ramping Mode is not
set to [`OFF] and Setup Page
Lock (Lockout Menu) is not set
to [hide].
1101 r/w10.0 (1)0.1 to 99.9 (1 to 999)
[rAtE] Ramp Rate**
Set the units or de-
grees set point ramp
rate.
Active if Local or Remote Mode
(User Menu) is not set to
[```r], Ramping Mode (Global
Menu) is not set to [`Off] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
1102 r/w
[Min] (0)[Min] minute (0)
[hour] hour (1)
[rp`S] Ramp Scale**
Set the single step
ramp scaling in de-
grees per hour or
minute.
Active if Local or Remote Mode
(User Menu) is not [```r] (re-
mote set point is not active)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
1100 r/w
[`OFF] (0)[`OFF] off (0)
[Strt] startup only (1)
[Stpt] startup or set
point change (2)
[``rP] Ramping Mode**
Set the single step
ramp to set point
mode.
Active if Setup Page Lock (Lock-
out Menu) is not set to [hide].
715 r/w100.0 (1000)0.0 to 100.0 (0 to 1000)
Applies to heat or cool.
[PL`b] High Power Limit
Below
Set high power limit
below the power
limit set point.
Active if Setup Page Lock (Lock-
out Menu) is not set to [hide].
714 r/w100.0 (1000)0.0 to 100.0 (0 to 1000)
Applies to heat or cool.
[PL`A] High Power Limit
Above
Set high power limit
above the power
limit set point.
Active if Setup Page Lock (Lock-
out Menu) is not set to [hide].
713 r/w
[rh`1] (1)[rL`1] Sensor Range
Low
[rh`1] Sensor Range
High
[PLSP] Power Limit Set
Point
Set point for power
limits, [PL`A] above
this point, [PL`b]
below.
Watlow Series 96 Parameters â–  6.17
Setup Page / Global Menu
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.