Manual
Active if output 4 is equipped for
retransmit (96 _ _-_ _ _ M-_ _ _
_), Analog Output 4 (Output 4
Menu) is set to [`OFF] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****
Sensor type
rh1
[A`Lo] Analog Output
Low to 9999
[A`hi] Analog Output
High
Set analog output
range high scaling.
Active if output 4 is equipped for
retransmit (96 _ _-_ _ _ M-_ _ _
_), Analog Output 4 (Output 4
Menu) is set to [`OFF] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****
Sensor type
rL1
-1999 to [A`hi] Analog
Output High
[A`Lo] Analog Output
Low
Set analog output
range low scaling.
Active if output 4 is equipped for
retransmit (96 _ _-_ _ _ M - _ _
_ _) and [Aout] (Analog Out-
put 4) is not set to [`OFF] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[4-20][4-20] 4-20 mA
[0-20] 0-20 mA
[0-`5] 0-5VÎ (dc)
[1-`5] 1-5VÎ (dc)
[0-10] 0-10VÎ (dc)
[Prc4] Process 4 Type
Set process 4 output
type.
Active if output 4 is equipped for
retransmit (96 _ _-_ _ _ M-_ _ _
_) and Setup Page Lock (Lock-
out Menu) is not set to [hide].
none****[`OFF][`OFF] not active
[proc] process
[``sp] set point
[pcnt] percent power
[Aout] Analog Output 4
Select Output 4 re-
transmit signal.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _),
Output 4 is Set to [``AL]
(Alarm) and Setup Page Lock
(Lockout Menu) is not set to
[hide].
none****[`yes][``no] no
[`Yes] yes
[Anu4] Alarm Annuncia-
tion 4
Select alarm 4 an-
nunciation option.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[al`0][al`0] alarm condition
de-energizes output
[al`C] alarm condition
energizes output
[Lgc4] Alarm Logic 4
Select alarm 4 out-
put condition in
alarm state.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[both][both] both
[``hi] high
[``lo] low
[Sid4] Alarm Active Sides
4
Select alarm 4 side
option.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D -_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[``no][``no] no action
[`yes] silence 4 en-
abled
[SIL4] Silencing 4
Enable Silence 4.
Watlow Series 96 Parameters ■ 6.15
Setup Page / Output 4 Menu
Display Parameter Range Default Modbus Conditions for 
(Modbus Value) Register Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.