Manual

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[``no][``no] no action
[`Yes] latching en-
abled
[Lat4] Latching 4
Enable alarm 4
latching.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D -_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****
3°F, 2°C1 to 9999
[ahy4] Alarm Hysteresis 4
Sets the switching
hysteresis for the
alarm output. This
defines a band on
the inside of the
alarm set point.
When the process
temperature is in
this band, the alarm
state will not
change.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none****[proc][proc] process alarm
[``de] deviation alarm
[AtY4] Alarm 4 Type
Select alarm 4 type.
Active if output 4 is equipped for
a relay (96 _ _-_ _ _ D-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
*Event output is added if ramp-
ing version of the controller is
selected (96__-____-AA__.)
none****[`OFF][`OFF] off
[``AL] alarm
[eunt] event*
[Ot`4] Output 4
Select output 4 type.
[Out4] Output 4 Menu
[`set] Setup Page
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ _), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to [hide].
742 r/w
[`Yes] (1)[``no] no (0)
[`Yes] yes (1)
[Anu3] Alarm
Annunciation 3
Select alarm 3
annunciation option.
Active if output 3 is present (96 _
_-_ _ D _-_ _ _ _), Output 3
(Output 3 Menu) is set to
[``AL] (Alarm) and Setup
Page Lock (Lockout Menu) is
not set to [hide].
741 r/w
[Al`O] (0)[Al`O] alarm condition
de-energizes output
(fail-safe operation)
(0)
[Al`C] alarm condition
energizes output (1)
[Lgc3] Alarm Logic 3
Select alarm 3 output
condition in the
alarm state.
6.14 Parameters Watlow Series 96
Setup Page / Output 4 Menu
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write
****Output 4 parameters cannot be changed with the Modbus interface.