Manual

Active if output 2 is present, but
is not process type ( not 96 _ _-
_ A _ _-_ _ _ __ or 96 _ _-_ F_ _-
_ _ _ _), Output 2 (Output 2
Menu) is set to [``AL] (Alarm)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
719 r/w
[Proc] (0)[Proc] process alarm
(0)
[``de] deviation alarm
(1)
[AtY2] Alarm 2 Type
Select alarm type.
A process alarm re-
sponds when the
temperature leaves
a fixed range.
A deviation alarm
responds when the
temperature devi-
ates from the set
point by a set num-
ber of degrees.
Active if output 2 is equipped for
a process (96 _ _-_ F_ _-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
718 r/w
[4-20] (0)[4-20] 4-20mA (0)
[0-20] 0-20mA (1)
[`0-5] 0-5VÎ (dc) (2)
[`1-5] 1-5VÎ (dc) (3)
[0-10] 0-10VÎ (dc) (4)
[Prc2] Process 2 Type
Sets output 2
process type.
Active if output 2 is present (not
96 _ _-_ A _ _-_ _ _ _) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
*Event output is added if ramp-
ing version of the controller is
selected (96__-____-AA__.)
717 r/w
[`OFF] (0)[`OFF] off (0)
[heat] heat (1)
[COOL] cool (2)
[``al] alarm (3)
[eunt] event (4)*
[Ot`2] Output 2
Select output 2
function.
[Out2] Output 2 Menu****
[`set] Setup Page
Active if output 1 is equipped for
a process (96 _ _-F _ _ _-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
701 r/w
[4-20] (0)[4-20] 4-20mA (0)
[0-20] 0-20mA (1)
[`0-5] 0-5VÎ (dc) (2)
[`1-5] 1-5VÎ (dc) (3)
[0-10] 0-10VÎ (dc) (4)
[Prc1] Process 1 Type
Sets process 1
output type.
Active if Setup Page Lock (Lock-
out Menu) is not set to [hide].
700 r/w
[heAt] (0)[heAt] heat (0)
[COOL] cool (1)
[Ot`1] Output 1
Select whether the
control output will
control for heating
or cooling.
[Out1] Output 1 Menu****
[`set] Setup Page
Active if [E`fn] is set to
[absp].
1211 r/w75°F, 24°C
[`Off],
Range Low 1 to Range
High 1 (-32768)
[absp] Abort Set Point
Active if input 2 hardware is pre-
sent (96 _1 _-_ _ _ _ -_ _ _ _),
Input 2 (Input 2 Menu) is set
to [E`In] (Event Input), Event
Function (Input 2 Menu) is not
set to [none] and Setup Page
Lock (Lockout Menu) is not set
to [hide].
1061 r/w
[``LO] (0)[``LO] low (0):
[``hi] high (1)
[rise] rise (2)
[FALL] fall (3)
[E`cn] Event Condition
Select the condition
to trigger an event.
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write
Watlow Series 96 Parameters 6.11
Setup Page / Output 2 Menu
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
****Output 1 and Output 2 menu prompts cannot have range selections set to identical control modes, e.g. Heat/Heat
or Cool/Cool if the ramping software option has been ordered (96 _ _ - _ ___- AA __ ) .