Manual
Active if input 2 hardware is pre-
sent (96 _1 _-_ _ _ _ -_ _ _ _)
and Input 2 (Input 2 Menu) is
set to [E`In] (Event Input)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
*[`we], [paus], [fil1],
[fil2], [hold], and [Absp]
are added if ramping version of
the controller is selected
(96__-____-AA__.)
**[``SP] and [A-M] are re-
moved if ramping version of
the controller is selected
(96__-____-AA__.)
1060 r/w
[nonE] (0)[none] no function (0)
[``SP] switch to event
set point (1)**
[AOFF] turn off control
outputs and disable
alarms (2)
[COFF] turn off control
outputs (3)
[`LOC] lock out key
board (4)
[A-M] switch to man-
ual mode (5)**
[tune] initiate an
auto-tune (6)
[``AL] clear alarm (7)
[SLOC] lock out every-
thing except primary
set point (auto or
manual). If selected
and if a profile is not
running (non-ramping
mode) will lock the
user out of all param-
eters except set point
and event outputs. (8)
[`we] wait-for event
input (9)*
[paus] pause (10)*
[fil1] profile 1 (11) *
[fil2] profile 2 (12) *
[hold] hold (13)*
[Absp] abort set point
(14)*
[E`Fn] Event Function
Select the event
function.
Active if input 2 hardware is pre-
sent (96 _1 _-_ _ _ _ -_ _ _ _),
and [In`2] is not set to
[E`In] or [`OFF] and Setup
Page Lock (Lockout Menu) is
not set to [hide].
615 r/w0-1999 to 9999
[CAL2] Calibration Offset
2**
Set the input calibra-
tion offset. This al-
lows you to compen-
sate for lead resis-
tance, sensor errors
and other factors.
Active if input 2 hardware is pre-
sent (96 _1 _-_ _ _ _ -_ _ _ _),
and [In`2] is not set to
[E`In] or [`OFF] and Setup
Page Lock (Lockout Menu) is
not set to [hide].
613 r/wrh1
[`rL2] Range Low 2 to
9999
[rh`2] Range High 2**
Set the input range
high. This setting is
the value [Pr`2]
will read when Input
2 is at its high
range.
Active if input 2 hardware is pre-
sent (96 _1 _-_ _ _ _ -_ _ _ _)
and [In`2] is not set to
[E`In] or [`OFF] and Setup
Page Lock (Lockout Menu) is
not set to [hide].
612 r/wrL1
-1999 to [`rh2] Range
High 2
[rL`2] Range Low 2**
Set the input range
low. This setting is
the value [Pr`2]
will read when Input
2 is at its low range.
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write
6.10 â– Parameters Watlow Series 96
*These parameters are added if the ramping software option has been ordered (96 _ _ - _ ___- AA __ ) .
**These parameters are removed if the ramping software option has been ordered (96 _ _ - _ ___- AA __ ) .
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
Setup Page / Input 2 Menu