NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.
Active if Output 3 (Output 3
Menu) is [``AL] (Alarm),
Alarm Sides 3 (Output 3 Menu)
is not [``hi], output 3 is pre-
sent (96 _ _-_ _ D _-_ _ _ _) and
Operations Page Lock (Lockout
Menu) is not set to [hide]
.
340 r/wProcess: low
limit of se-
lected sen-
sor range
Deviation:
-999
Process: low limit of se-
lected sensor range
to Alarm 3 High-1
Deviation: -1999 to 0
[A3Lo] Alarm 3 Low
Set the low alarm
set point for output
3.
Active if Output 2 (Output 2
Menu) is set to [``AL] (Alarm),
Alarm Active Sides 2 (Output 2
Menu) is not set to [``lo], out-
put 2 is present, but is not a
process (not 96 _ _-_ A _ _-_ _ _
_ or 96 _ _-_ F_ _-_ _ _ _) and
Operations Page Lock (Lockout
Menu) is not set to [hide].
322 r/wProcess: high
limit of se-
lected sen-
sor range
Deviation:
999
Process: Alarm 2
Low+1 to high limit
of selected sensor
range
Deviation: 0 to 9999
[A2hi] Alarm 2 High
Set the high alarm
set point for output
2.
Active if Output 2 (Output 2
Menu) is set to [``AL] (Alarm),
Alarm Active Sides 2 (Output 2
Menu) is not set to [``hi], out-
put 2 is present, but is not a
process output (not 96 _ _-_ A _
_-_ _ _ _ or 96 _ _-_ F_ _-_ _ _ _)
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
321 r/wProcess: low
limit of se-
lected sen-
sor range
Deviation:
-999
Process: low limit of se-
lected sensor range
to Alarm 2 High-1
Deviation: -1999 to 0
[A2Lo] Alarm 2 Low
Set the low alarm
set point for output
2.
[Alm] Alarm Menu
[Oper] Operations Page
Active if output 2 is present (not
96 _ _-_ A _ _-_ _ _ _), one out-
put is set to [heat], another is
set to [COOL] and Operations
Page Lock (Lockout Menu) is
not set to [hide].
515 r/w0 (0)0 to 9999
[db`2] Dead Band 2
Set point shift for
output 2 control.
Active if Output 2 is present, but
output 2 is not a process type
(not 96 _ _-_ A _ _-_ _ _ _ or 96
_ _-_ F_ _-_ _ _ _), or Output 2
(Output 2 Menu) is set to
[hEAt] or [COOL] (opposite of
Output 1 [hEAt] or [COOL] se-
lection); and Propband 2 (PID
2 Menu) is set to [```0] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
517 r/w3°F, 2°C1 to 9999
[hys2] Hysteresis 2
Sets the switching
hysteresis for output
2.
6.6 ■ Parameters Watlow Series 96
Operations Page / Alarm Menu
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write