Manual

Active if Propband 1(PID 1 Menu)
is not set to [```0], Units Type
(Global Menu) is set to [``US]
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
502 r/w0.00 (0)0.00 to 99.99 repeats
per minute
[rE`1] Reset 1
Set the reset time in
repeats/minute for
output 1.
Active if Propband 1(PID 1 Menu)
is not set to [```0], Units Type
(Global Menu) is set to [``SI]
and Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
501 r/w0.00 (0)0.00 to 99.99 minutes
per repeat
[It`1] Integral 1
Set the integral time
in minutes for out-
put 1.
Active if Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
500 r/w25°F, 14°C 0° to 9999°
If [Pb`1] is set to 0 op-
erates in on/off mode.
[Pb`1] Propband 1
Set the proportional
band for PID con-
trol.
[Pid1] PID 1 Menu
[Oper] Operations Page
Active if Operations Page (Lock-
out Menu) is not set to [hide]
.
605 r/w0-1999 to 9999
[CAL1] Calibration Offset
Set the input 1 cali-
bration offset.
Active if Input 2 (Input 2 Menu)
is not set to [`Off], Input 2 is
not set to [E`In] (event input)
and Operations Page Lock
(Lockout Menu) is not set to
[hide]
.
316 r/w
[```L] (0)[```L] local (0)
[~~~r] remote (1)
[`L-r] Local or Remote
Mode**
Set the mode to local
or remote set point.
Active if output 2 is present (not
96 _ _-_ A _ _-_ _ _ _), both Out-
put 1 (Output 1 Menu) and
Output 2 (Output 2 Menu) are
set to either [heat] or [COOL]
and Operations Page Lock
(Lockout Menu) is not set to
[hide].
319 r/w75°F, 24°CRange Low 1 to Range
High 1
[`SP2] Set Point 2**
Set the boost set
point.
Active if Input 2 (Input 2 Menu)
is set to [e`In] (event input),
[E`Fn] is set to [``SP], and
Operations Page Lock (Lockout
Menu) is not set to [hide].
306 r/w75°F, 24°CRange Low 1 to Range
High 1
[E`SP] Event Set Point2**
Set the set point
when the event
input is active as de-
fined by Event Con-
dition.
Active if Operations Page Lock
(Lockout Menu) is not set to
[hide].
304 r/w9050 to 150
[AtSP] Auto-tune Set
Point
Set the auto-tune set
point as a percent of
the currently active
set point.
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Register Parameters to Appear
read/write
Watlow Series 96 Parameters 6.3
Operations Page / PID 1 Menu
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.