Instruction Manual

Tuning and Operating, Chapter 6
45
WATLOW Series 942 User's Manual
Errors/Outputs
Error Code Actions
Error codes Er 1, Er 2, Er 3, Er 6, and Er 7 will result in these conditions:
Control outputs turn OFF.
The auxiliary output (if present and programmed as an alarm) will be in
the alarm state (LED lit). If programmed as an event, the output turns
OFF.
• The Upper display will read "- - - -".
The Lower display indicates the error code.
The HOLD/RUN and MODE keys are inactive. The UP/DOWN keys
may be used together to enter the Setup Menu.
To clear a corrected error…
• Cycle power to the control, or MODE through the SETUP menu until
you return to the set point.
If an error occurs while in the RUN mode, the program cannot be resumed.
Set point defaults to the previous value.
Error codes Er 4 and Er 5 will result in these conditions:
• Control outputs turn OFF.
• The auxiliary outputs, if present, are in their alarm state (de-energized
with the LED lit).
The Upper display indicates "- - - -".
• The Lower display indicates the error code.
• All Keys are inactive.
All Setup Menu parameters return to default values.
The above conditions will occur regardless of the value of LOC, or the
presence of the Setup or Calibration Menus.
To clear a corrected error…
• Cycle power to the control.