Instruction Manual

Setup, Chapter 4
30
WATLOW Series 942 User's Manual
Operation
Operation Parameters Value Range Factory Default
SP OFF/rL to rH 75°F
Prog YES or no no
Ent1 On or OFF OFF
Ent2 On or OFF OFF
Pb1 If dFL = US: 0 - 999°F/0 - 555°C/0 - 999 Units 25°F
0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units
If dFL = SI: 0 to 999.9% 3.0%
0 = ON/OFF control. HYS1 = switch. diff.
Pb2 Same as Pb1. Will not appear if Ot 2 = no. 0°
rE1/It1 Reset: 0.00 to 9.99 repeats/min. 0.00 repeats/min.
Integral: 0 and 00.1 to 99.9 min./repeat
0.00 = no reset. Will not appear if Pb1 = 0.
rE2/It2 Same as rE1. Will not appear if Pb2 = 0. 0.00 repeats/min.
rA1/dE1 0.00 to 9.99 min. 0.00 min.
0.00 = No Rate. Will not appear if Pb1 = 0
rA2/dE2 Same as rA1. Will not appear if Pb2 = 0. 0.00 min.
Ct1 1 to 60 seconds 5 seconds
Won't appear if Pb1 = 0, or output 1 is 4-20
Ct2 1 to 60 seconds 5 seconds
Will not appear if Pb2 = 0 or Ot2 = no.
db ± 0 - 99°F/± 0 - 55°C/0 - 99 Units. 0
± 0.0 - 9.9°F/0.0 - 5.5°C/0.0 - 9.9 Units
Appears if ht/CL or CL/ht.
A1LO - Deviation dE -999° to 0° -999°
Process Pr rL to A1HI rL
Appears if auxiliary output and Ot3 = AL.
A1HI - Deviation dE 0° to 999° 999°
Process Pr A1LO to rH rH
Appears if auxiliary output and Ot3 = AL.
A2LO- Deviation dE -999° to 0° -999
Process Pr rL to A2HI rL
Appears if auxiliary output and Ot4 = AL.
A2HI- Deviation dE 0° to 999° 999°
Process Pr A2LO to rH rH
Appears if auxiliary output and Ot4 = AL.
CAL ± 99°F/± 55°C/± 99 Units 0
AUt 0 to 3 0
Table 3 -
Operation Menu Parameters and Descriptions.
Alarm 1 High: This parameter represents the high process alarm or high deviation
alarm for Alarm 1. This parameter appears if your unit has an auxiliary output and
Ot3 = AL. See the model number. If AL 1 = Pr: Range: A1LO to rH Default: rH
AL 1 = dE: Range: 0 to -999°F/0 to -999°C/0 to -999 Units Default: -999°F
Alarm 2 Low: Represents the low process alarm or low deviation alarm for
Alarm 2. Appears if your unit has an auxiliary output and Ot4 = AL. See the model
number. If AL 2 = Pr: Range: rL to A2HI Default: rL
If AL 2 = dE: Range: 0 to -999°F/0 to -999°C/0 to -999 Units Default: -999°F.
Alarm 2 High: Represents the high process alarm or high deviation alarm for
Alarm 2. Appears if your unit has an auxiliary output and Ot4 = AL. See the model
number. If AL 2 = Pr: Range: A2LO to rH Default: rh
If AL 2 = dE: Range: 0 to -999°F/0 to -999°C/0 to -999 Units Default: -999°F
Calibration Offset: Adds or subtracts degrees from the input signal.
Range: -99°F to 99°F/-55°C to 55°C/-99 Units to 99 Units; or -99.9°F to
99.9°F/-55.5°C to 55.5°C Default: 0
Auto-Tune: This parameter initiates auto-tune for Output 1 in the heating mode
only. This parameter appears if Ot1 = ht. For more information on Tuning see
Chapter 6. Range: 0 = off, 1 = slow, 2 = medium, 3 = fast Default: 0