Instruction Manual
Setup, Chapter 4 WATLOW Series 942 User's Manual
27
Setup
Use this page as a master copy for configuring your Series 942.
Do not enter any values here; make photocopies instead.
Setup Parameters Value Range Factory Default
LOC 0 to 3 0
In J, K (appears as H), t, n, c, r, S, b, J or r
Pt2, rtd1, rtd.1, 0-5, 420
Dependent on model number.
dEC 0, 0.0, or 0.00 0
Dependent on input type.
C _ F C or F F
Will not appear if In = 0-5 or 420.
rL rL to rH Input selection dependent.
rH rH to rL Input selection dependent.
Ot1 ht or CL ht
HYS1 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
Ot2 ht, CL or no CL
HYS2 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
Ot3 AL, Ent or no AL
AL1 Pr or dE Pr
LAt 1 LAt or nLA nLA
Dependent on AL 1 = Pr or dE.
HYS3 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
SIL On or OFF OFF
Ot4 AL, Ent, no, PrOC or StPt AL or PrOC
AL 2 Pr or dE Pr
LAt 2 LAt or nLA nLA
HYS4 1°F - 999°F, 1°C - 540°C, 1U - 999U 3°F
0.1°F - 99.9°F, 0.1°C - 54.0°C, 0.1U - 99.9U
rtd JIS or din din
PtYP ti or rAtE ti
gSd 0 - 99°F, 0 - 55°C, 0 - 99U 0
0.0 - 9.9°F, 0.0 - 5.5°C, 0.0U - 9.9U
POUt Cont, HOLd, Abrt or rSET Cont
PStr Proc or StPt StPt
bAUd 300, 600, 1200, 2400, 4800, 9600 1200
dAtA 7 o = Odd parity, 7 E = Even parity 7 o
8 n = 8 data bits and no parity
Prot FULL or On FULL
Addr 0 to 31 0
Log On or OFF OFF
Int 0.0 to 60.0 minutes 0.0
tag PSA, PS-, P-A, P--, -SA, ---
-S-, --A, ---
P = Process, S = Set point
A = Auxiliary Status
Table 2 -
Setup Menu Parametersand Descriptions.