Instruction Manual

Setup, Chapter 4
26
WATLOW Series 942 User's Manual
Setup
dAtA
bAud
Addr
Prot
LOg
Int
tAg
PStr
Input Type Sensor Range Low Sensor Range High
J32°F/0°C 1382°F/750°C
K (appears as H) -328°F/-200°C 2282°F/1250°C
t -328°F/-200°C 662°F/350°C
n32°F/0°C 2282°F/1250°C
Pt2 32°F/0°C 2543°F/1395°C
c 797°F/425°C 4200°F/2315°C
r32°F/0°C 2642°F/1450°C
S32°F/0°C 2642°F/1450°C
b *32°F/0°C 3092°F/1700°C
rtd (1°) -328°F/-200°C 1112°F/600°C
rt.d (0.1°) -99.9°F/-99.9°C 392.0°F/200.0°C
0-5 (VDC) -5.00/-50.0/-500 35.00/350.0/3500
420 (mA) -5.00/-50.0/-500 35.00/350.0/3500
* b t/c: Useable
range is suggested
to be 1598 to 3092°F
or 870 to 1700°C.
Range is at 32° to
allow using at low
temperatures
without range low
sensor errors.
NOTE:
Profile Start: Selects whether the profile starts at the current set point value or
the current process value.
Range: Proc or StPt Range: StPt
Baud: Represents the current baud rate for serial communications. This
parameter appears if your Series 942 has communications.
Range: 300, 600, 1200, 2400, 4800, 9600 Default: 1200
Data: Allows the user to select the data bits and parity for communication.
This parameter appears if your Series 942 has communications.
Range: 7 o = 7 data bits and odd parity Default: 7 o
7 E = 7 data bits and even parity
8 n = 8 Data bits and no parity
Protocol: Selects the communication protocol. This parameter appears if your
Series 942 has communications.
FULL = ANSI X3.28 2.2 - A.3 On = XON - XOFF
Range: FULL or On Default: FULL
Address: Selects the address for this unit if Prot = FULL. This parameter
appears if your Series 942 has communications.
Range: 0 to 31 Default: 0
Log: Selects the data logging function for a printout of the data. This parame-
ter appears if your Series 942 has communications, and Prot = On.
Range: On or OFF Default: OFF
Interval: Selects the time interval for the logging function This parameter
appears if your Series 942 has communications, Prot = On, and Log = On.
Range: 0.0 to 60.0 minutes Default: 0.0
Tag: Selects what variables are to be transmitted out during the data logging
function. This parameter appears if your Series 942 has communications,
Prot = On, and Log = On.
P = Process S = Set Point A = Auxiliary Status
Range: PSA, PS-, P-A, P--, -SA, -S-, --A, --- Default: ---
Table 1- Input Ranges