Ordering Information—(1952) 9 3 5 B - 1 C C 0 - _ _ 0 _
Single thermocouple or RTD (DIN) input,
dual output, single display temperature
control with time function
Output 1/Remote Input
C = Switched dc, logic signal, non-isolated
Output 2
C = Switched dc, logic signal, non-isolated
Power Supply
0 = 100 to 240VÅ (ac)
Custom Options
00 = None
AA-ZZ = Consult factory for options
Display
R=Red Displays
G=Green Displays
Table 15 - Input Range Information
J t/c: 32 to 1382°F or 0 to 750°C
K t/c: -328 to 2282°F or -200 to 1250°C
T t/c: -328 to 662°F or -200 to 350°C
N t/c: 32 to 2282°F or 0 to 1250°C
S t/c: 32 to 2642°F or 0 to 1450°C
E t/c: -328 to 1470°F or -200 to 799°C
1° RTD (DIN): -328 to 1292°F or -200 to 700°C
0.1° RTD: -99.9 to 999.9°F or -99.9 to 700.0°C
1
To effect NEMA 4X (IP65) rating requires a minimum
mounting panel thickness of 0.06 inch (1.5mm) and a
surface finish not rougher than 0.000032 inch (0.000812 mm).
Watlow Series 935B User’s Manual 49
Ordering a 935B