Manual

24 Watlow Series 935A Users Manual
Configuration Menu
[``In]
Input Type
[`C_F]
Celsius/Fahrenheit
[``rL]
Input Range Low
[``rh]
Input Range High
[`Ot1]
Output 1 Function
[`Ot2]
Output 2 Function
[dISP]
Display Default
[ALtY]
Alarm Type
[AhYS]
Alarm Hysteresis
[`LAt]
Alarm Latch
[`SIL]
Alarm Silencing
[FAIL]
Failure Mode
Operations
Menu
[`Aut]
Auto-tune
[`ALO]
Alarm Range Low
[`AhI]
Alarm Range High
[`Pid]
PID
[CnFG]
Configuration
Learning Alarms
Alarms signal an excursion from normal operating conditions. In general, audible alarms or lights
connected to alarm outputs will signal a problem. In the 935A the front panel LED 1 or 2 indicates an
alarm with [``hI] or [``LO] flashing on the main display.
Process alarms use absolute high and low values to trigger an alarm. Use this alarm type if your
process may be subject to temperatures that it must not exceed. Use [`AhI] and [`ALO] to set
alarm points at or near these values. See Table 10: [ALtY], next page.
Deviation alarms are triggered by a deviation from the set point. The alarm high value [`AhI] is
the deviation above set point, and the low value [`ALO] is the deviation below set point. Whenever
the set point is adjusted, the alarm settings are relative to that value. Deviation alarms use the cur-
rently controlling set point, whether primary, remote, idle, or 90% of primary, during auto-tuning. See
Table 10: [ALtY], next page.
Normally Open, [dEno] or [Prno], Alarms energize the alarm output when an alarm condition
occurs, and de-energize it when cleared. Use this type to activate external devices such as audible
alarms or lights. See Table 10: [ALtY], next page.
Normally Closed, [dEnc] or [Prnc], Alarms de-energize the alarm output when an alarm condi-
tion occurs, and energize it when the alarm is cleared. Use this type as a deadman switch where
system continuity is required for operation. See Table 10: [ALtY], next page.
For example, by running the control output through the alarm output, you can set a normally
closed process alarm to disable the process when the process exceeds the alarm set point.
The alarm output will be off when power is off.
Alarm Hysteresis sets a point the process must pass on a return (from an alarm condition excur-
sion) to the [`ALO] and [`AhI] points before the alarm can clear. This prevents the alarm output
from chattering if the process is hovering around the alarm set point. See Table 10: [AhYS], next
page.
Latching Alarms require the operator to clear them with a ß press after the process returns to a
safe, or non-alarm condition. Non-latching alarms self-clear. See Table 11: [`LAt], p. 27.
Silenced Alarms provide a means to clear the alarm output with a ß press even if the alarm
condition still exists. The flashing [``hI] or [``LO] message will persist until the alarm condition
ceases. See Table 11: [`SIL], p. 27. If [`SIL] = [`YES], alarms are disabled (no message or
output) on startup until the safe area is reached.
Alarm High and Low Points, [`AhI] and [`ALO], in the Operations menu determine where
alarms will trigger. Alarm hysteresis [AhYS] determines where an alarm condition clears. See Table
11, page 27.
To Clear an Alarm that is latched or silence-able requires the operator to press the ß key after
the process returns to a safe, or non-alarm condition. Non-latching alarms self-clear. See Table 11:
[`LAt] and [`SIL], p. 27.
Table 10 (p. 25) and Table 11 (p. 27) illustrate the Series 935A alarm features.