Using This Retrofit Guide This document is best viewed with Adobe Reader 6.0. To obtain the latest version of Adobe Reader, visit http://www.adobe.com Specification sheets on Watlow product may be obtained at http://www.watlow.com/literature/specsheets/ User Manuals on Watlow product may be obtained at http://www.watlow.com/literature/prodtechinfo/ Additional information on other Watlow products may be obtained by visiting http://www.watlow.
Abbreviation & Terminology (as used in this document) 0.5 – 0.5 amperes of current switching capability 2A – 2 amperes of current switching capability 5A - 5 amperes of current switching capability 10A – 10 amperes of current switching capability 15A – 15 amperes of current switching capability 12-24 – Supply voltage can be between 12 to 24 Volts 100-240 – Supply voltage can be between 100 to 240 Volts 100 ohm DIN – refers to 100-ohm platinum RTD that has a DIN curve.
Integral – the set point in integral (on board) to the controller. JIS – Joint Industrial Standards, a set of technical, scientific and dimensional standards developed in Japan. RTD sensors with the JIS curve change resistance at a rate of 0.00396 ohms/ohms/C. Line Voltage – the voltage required powering the electronics of the controller. Low Limit - device will deactivate output on a temperature drop below set point.
VTB Sw DC – Variable Time Base Switched Direct Current, a time proportioning DC output where the cycle time is variable.
These notes are used to signify areas of concern in changing to a retrofit choice. These notes are also printed at the end of the retrofit listing. Note 1: Retrofit controller requires a substitution of a 100 Ohm RTD sensor for the thermistor. Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is available. Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable.
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Manual Reset 3A Relay Remote Potted LV C1HU 0140 0294 A 2, 6, 8 Remote Potted LV C1JU 0060 0146 A 2, 6, 8 Remote Potted LV C1HW 0140 0294 A 2, 6, 8 142A-2676-1200 120 VAC J t/c 140 to 294°F High limit 142A-2676-1200 120 VAC J t/c 60 to 146°C High limit Manual Reset 3A Relay 142A-2676-1300 120 VAC J t/c 140 to 294°F High limit Automatic Reset 3A
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Heat 3A Relay Remote Potted CV C1JH 0093 0316 A Remote Potted LV E1HU 0200 0600 A 2, 6, 8 142A-2702-1400 120 VAC J t/c 93 to 316°C On/Off 142A-2702-2200 230 VAC J t/c 200 to 600°F High limit Manual Reset 3A Relay 2, 6, 8 142A-2702-2200 230 VAC J t/c 93 to 316°C High limit Manual Reset 3A Relay Remote Potted LV E1JU 0093 0316 A 2, 6, 8 142A-2702
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Heat 3A Relay Remote Potted CV E1HH 0032 0302 A Remote Potted CV E1JH 0000 0150 A 2, 6, 8 142A-2720-2400 230 VAC J t/c 32 to 302°F On/Off 142A-2720-2400 230 VAC J t/c 0 to 150°C On/Off Heat 3A Relay 2, 6, 8 142A-2732-1200 120 VAC E t/c 68 to 617°F High limit Manual Reset 3A Relay Remote Potted LV C1SU 0068 0617 A 2, 6, 8 142A-2732-1200 120 VAC
Series 142 Series 142 Line Voltage Input 142A-3601-1300 120 VAC J t/c 142A-3601-1300 120 VAC J t/c 142A-3601-1400 120 VAC J t/c 225°F On/Off 142A-3601-1400 120 VAC J t/c 107°C On/Off Heat 3A Relay Fixed Potted CF C4JH 0107 AAAA A 6, 8 142A-3601-2200 230 VAC J t/c 225°F High limit Manual Reset 3A Relay Fixed Potted LF E4HU 0225 AAAA A 6, 8 Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 225°F High limit Automatic Reset 3A Relay
Series 142 Series 142 Line Voltage Temp Range Control Mode Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF E4JU 0149 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF E4HW 0300 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF E4JW 0149 AAAA A 6, 8 6, 8 142A-3604-2200 230 VAC J t/c 149°C High limit 142A-3604-2300 230 VAC J t/c 300°F High limit 142A-3604-2300 230 VAC J t/c 149°C High limit Retrofit See Notes Below Input 142A-3604-2400
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Manual Reset 3A Relay Fixed Potted LF C4HU 0400 AAAA A 6, 8 Fixed Potted LF C4JU 0204 AAAA A 6, 8 Fixed Potted LF C4HW 0400 AAAA A 6, 8 142A-3608-1200 120 VAC J t/c 400°F High limit 142A-3608-1200 120 VAC J t/c 204°C High limit Manual Reset 3A Relay 142A-3608-1300 120 VAC J t/c 400°F High limit Automatic Reset 3A Relay 142A-3608-1300 120 VAC
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3611-1400 120 VAC J t/c 116°C On/Off Heat 3A Relay Fixed Potted CF C4JH 0116 AAAA A 6, 8 142A-3611-2200 230 VAC J t/c 240°F High limit Manual Reset 3A Relay Fixed Potted LF E4HU 0240 AAAA A 6, 8 142A-3611-2200 230 VAC J t/c 116°C High limit Manual Reset 3A Relay Fixed Potted LF E4JU 0116 AAAA A 6, 8 142A-3611-2300 230 VAC J t/c 240°F
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Heat Output Retrofit See Notes Below Set Point Mounting 3A Relay Fixed Potted CF E4HH 0525 AAAA A Fixed Potted CF E4JH 0274 AAAA A 6, 8 142A-3614-2400 230 VAC J t/c 525°F On/Off 142A-3614-2400 230 VAC J t/c 274°C On/Off Heat 3A Relay 6, 8 142A-3615-1200 120 VAC J t/c 550°F High limit Manual Reset 3A Relay Fixed Potted LF C4HU 0550 AAAA A 6, 8 142A-3615-1200 120 VAC J t/c 288°C High limit M
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action 142A-3618-1300 120 VAC J t/c 329°C High limit Automatic Reset 3A Relay Fixed Potted LF C4JW 0329 AAAA A 6, 8 142A-3618-1400 120 VAC J t/c 625°F On/Off Heat 3A Relay Fixed Potted CF C4HH 0625 AAAA A 6, 8 142A-3618-1400 120 VAC J t/c 329°C On/Off Heat 3A Relay Fixed Potted CF C4JH 0329 AAAA A 6, 8 Output Set Point Mounting Retrofit See Notes Below 142A-3618-2200 230 VAC J t/c 625°F High limi
Series 142 Series 142 Line Voltage Input 142A-3621-2300 230 VAC J t/c 142A-3621-2300 230 VAC J t/c 142A-3621-2400 230 VAC J t/c 700°F On/Off 142A-3621-2400 230 VAC J t/c 371°C On/Off Heat 3A Relay Fixed Potted CF E4JH 0371 AAAA A 6, 8 142A-3622-1200 120 VAC J t/c 725°F High limit Manual Reset 3A Relay Fixed Potted LF C4HU 0725 AAAA A 6, 8 Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 700°F High limit Automatic Reset 3A Relay
Series 142 Series 142 Line Voltage Temp Range Control Mode Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF C4JU 0427 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF C4HW 0800 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF C4JW 0427 AAAA A 6, 8 6, 8 142A-3625-1200 120 VAC J t/c 427°C High limit 142A-3625-1300 120 VAC J t/c 800°F High limit 142A-3625-1300 120 VAC J t/c 427°C High limit Retrofit See Notes Below Input 142A-3625-1400
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Manual Reset 3A Relay Fixed Potted LF E4HU 0875 AAAA A 6, 8 Fixed Potted LF E4JU 0468 AAAA A 6, 8 Fixed Potted LF E4HW 0875 AAAA A 6, 8 142A-3628-2200 230 VAC J t/c 875°F High limit 142A-3628-2200 230 VAC J t/c 468°C High limit Manual Reset 3A Relay 142A-3628-2300 230 VAC J t/c 875°F High limit Automatic Reset 3A Relay 142A-3628-2300 230 VAC
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3631-2400 230 VAC J t/c 510°C On/Off Heat 3A Relay Fixed Potted CF E4JH 0510 AAAA A 6, 8 142A-3632-1200 120 VAC J t/c 975°F High limit Manual Reset 3A Relay Fixed Potted LF C4HU 0975 AAAA A 6, 8 142A-3632-1200 120 VAC J t/c 524°C High limit Manual Reset 3A Relay Fixed Potted LF C4JU 0524 AAAA A 6, 8 142A-3632-1300 120 VAC J t/c 975°F
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3635-1400 120 VAC K t/c 1100°F On/Off Heat 3A Relay Fixed Potted CF C4KH 1100 AAAA A 6, 8 142A-3635-1400 120 VAC K t/c 537°C On/Off Heat 3A Relay Fixed Potted CF C4LH 0537 AAAA A 6, 8 142A-3635-2200 230 VAC K t/c 1100°F High limit Manual Reset 3A Relay Fixed Potted LF E4KU 1100 AAAA A 6, 8 6, 8 142A-3635-2200 230 VAC K t/c 537°C High
Series 142 Series 142 Line Voltage Input 142A-3638-2300 230 VAC 142A-3638-2400 230 VAC 142A-3638-2400 230 VAC Output Set Point Mounting Retrofit See Notes Below Temp Range Control Mode Action K t/c 677°C High limit Automatic Reset 3A Relay Fixed Potted LF E4LW 0677 AAAA A 6, 8 K t/c 1250°F On/Off Heat 3A Relay Fixed Potted CF E4KH 1250 AAAA A 6, 8 K t/c 677°C On/Off Heat 3A Relay Fixed Potted CF E4LH 0677 AAAA A 6, 8 142A-3639-1200 120 VAC K t/c 1300°F High li
Series 142 Series 142 Line Voltage Input Temp Range 142A-3642-1300 120 VAC K t/c 142A-3642-1300 120 VAC K t/c 142A-3642-1400 120 VAC K t/c Retrofit See Notes Below Control Mode Action Output Set Point Mounting 1450°F High limit Automatic Reset 3A Relay Fixed Potted LF C4KW 1450 AAAA A 6, 8 788°C High limit Automatic Reset 3A Relay Fixed Potted LF C4LW 0788 AAAA A 6, 8 1450°F On/Off Heat 3A Relay Fixed Potted CF C4KH 1450 AAAA A 6, 8 6, 8 142A-3642-1400 120 VAC K
Series 142 Series 142 Line Voltage Input Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF E4LU 0871 AAAA A Automatic Reset 3A Relay Fixed Potted LF E4KW 1600 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF E4LW 0871 AAAA A 6, 8 142A-3645-2200 230 VAC K t/c 871°C High limit 142A-3645-2300 230 VAC K t/c 1600°F High limit 6, 8 142A-3645-2300 230 VAC K t/c 871°C High limit 142A-3645-2400 230
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3649-1200 120 VAC K t/c 1800°F High limit Manual Reset 3A Relay Fixed Potted LF C4KU 1800 AAAA A 6, 8 142A-3649-1200 120 VAC K t/c 982°C High limit Manual Reset 3A Relay Fixed Potted LF C4LU 0982 AAAA A 6, 8 142A-3649-1300 120 VAC K t/c 1800°F High limit Automatic Reset 3A Relay Fixed Potted LF C4KW 1800 AAAA A 6, 8 142A-3649-1300 120 VA
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Heat 3A Relay Fixed Potted CF C4LH 1066 AAAA A Fixed Potted LF E4KU 1950 AAAA A 6, 8 6, 8 142A-3652-1400 120 VAC K t/c 1066°C On/Off 142A-3652-2200 230 VAC K t/c 1950°F High limit Manual Reset 3A Relay 6, 8 142A-3652-2200 230 VAC K t/c 1066°C High limit Manual Reset 3A Relay Fixed Potted LF E4LU 1066 AAAA A 142A-3652-2300 230 VAC K t/c 1950°F
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3655-2400 230 VAC K t/c 2100°F On/Off Heat 3A Relay Fixed Potted CF E4KH 2100 AAAA A 6, 8 142A-3655-2400 230 VAC K t/c 1149°C On/Off Heat 3A Relay Fixed Potted CF E4LH 1149 AAAA A 6, 8 142A-3656-1200 120 VAC K t/c 2150°F High limit Manual Reset 3A Relay Fixed Potted LF C4KU 2150 AAAA A 6, 8 6, 8 142A-3656-1200 120 VAC K t/c 1177°C Hig
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action 142A-3659-1300 120 VAC K t/c 1260°C High limit Automatic Reset 3A Relay Fixed Potted LF C4LW 1260 AAAA A 6, 8 142A-3659-1400 120 VAC K t/c 2300°F On/Off Heat 3A Relay Fixed Potted CF C4KH 2300 AAAA A 6, 8 142A-3659-1400 120 VAC K t/c 1260°C On/Off Heat 3A Relay Fixed Potted CF C4LH 1260 AAAA A 6, 8 Output Set Point Mounting Retrofit See Notes Below 142A-3659-2200 230 VAC K t/c 2300°F High
Series 142 Series 142 Line Voltage Input 142A-3662-2300 230 VAC K t/c 142A-3662-2300 230 VAC K t/c 142A-3662-2400 230 VAC K t/c 2450°F Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 2450°F High limit Automatic Reset 3A Relay Fixed Potted LF E4KW 2450 AAAA A 6, 8 1343°C High limit Automatic Reset 3A Relay Fixed Potted LF E4LW 1343 AAAA A 6, 8 On/Off Heat 3A Relay Fixed Potted CF E4KH 2450 AAAA A 6, 8 142A-3662-2400 230 VAC K t/c
Series 142 Series 142 Line Voltage Input Temp Range Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF C4JU 0063 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF C4HW 0145 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF C4JW 0063 AAAA A 6, 8 6, 8 142A-3666-1200 120 VAC J t/c 63°C High limit 142A-3666-1300 120 VAC J t/c 145°F High limit 142A-3666-1300 120 VAC J t/c 63°C High limit Retrofit See Notes Below Control Mode 142A-3666-1400 12
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Manual Reset 3A Relay Fixed Potted LF E4SU 0383 AAAA A 6, 8 Fixed Potted LF E4TU 0110 AAAA A 6, 8 Fixed Potted LF E4SW 0383 AAAA A 6, 8 142A-3669-2200 230 VAC E t/c 383°F High limit 142A-3669-2200 230 VAC E t/c 110°C High limit Manual Reset 3A Relay 142A-3669-2300 230 VAC E t/c 383°F High limit Automatic Reset 3A Relay 142A-3669-2300 230 VAC
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3672-2400 230 VAC J t/c 85°C On/Off Heat 3A Relay Fixed Potted CF E4JH 0085 AAAA A 6, 8 142A-3673-1200 120 VAC K t/c 1198°F High limit Manual Reset 3A Relay Fixed Potted LF C4KU 1198 AAAA A 6, 8 142A-3673-1200 120 VAC K t/c 648°C High limit Manual Reset 3A Relay Fixed Potted LF C4LU 0648 AAAA A 6, 8 142A-3673-1300 120 VAC K t/c 1198°F
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3677-1400 120 VAC K t/c 788°F On/Off Heat 3A Relay Fixed Potted CF C4KH 788 AAAA A 6, 8 142A-3677-1400 120 VAC K t/c 420°C On/Off Heat 3A Relay Fixed Potted CF C4LH 0420 AAAA A 6, 8 142A-3677-2200 230 VAC K t/c 788°F High limit Manual Reset 3A Relay Fixed Potted LF E4KU 788 AAAA A 6, 8 6, 8 142A-3677-2200 230 VAC K t/c 420°C High limi
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action 142A-3680-2300 230 VAC T t/c 16°C High limit Automatic Reset 3A Relay Fixed Potted LF E4NW 0016 AAAA A 6, 8 142A-3680-2400 230 VAC T t/c 60°F On/Off Heat 3A Relay Fixed Potted CF E4MH 0060 AAAA A 6, 8 142A-3680-2400 230 VAC T t/c 16°C On/Off Heat 3A Relay Fixed Potted CF E4NH 0016 AAAA A 6, 8 Output Set Point Mounting Retrofit See Notes Below 142A-3681-1200 120 VAC J t/c 175°F High limit
Series 142 Series 142 Line Voltage Input 142A-3684-1300 120 VAC E t/c 142A-3684-1300 120 VAC E t/c 142A-3684-1400 120 VAC E t/c 450°F On/Off 142A-3684-1400 120 VAC E t/c 232°C On/Off Heat 3A Relay Fixed Potted CF C4TH 0232 AAAA A 6, 8 142A-3684-2200 230 VAC E t/c 450°F High limit Manual Reset 3A Relay Fixed Potted LF E4SU 0450 AAAA A 6, 8 Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 450°F High limit Automatic Reset 3A Relay
Series 142 Series 142 Line Voltage Temp Range Control Mode Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF E4JU 0102 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF E4HW 0215 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF E4JW 0102 AAAA A 6, 8 6, 8 142A-3688-2200 230 VAC J t/c 102°C High limit 142A-3688-2300 230 VAC J t/c 215°F High limit 142A-3688-2300 230 VAC J t/c 102°C High limit Retrofit See Notes Below Input 142A-3688-2400
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3692-1200 120 VAC K t/c 2000°F High limit Manual Reset 3A Relay Fixed Potted LF C4KU 2000 AAAA A 6, 8 142A-3692-1200 120 VAC K t/c 1093°C High limit Manual Reset 3A Relay Fixed Potted LF C4LU 1093 AAAA A 6, 8 142A-3692-1300 120 VAC K t/c 2000°F High limit Automatic Reset 3A Relay Fixed Potted LF C4KW 2000 AAAA A 6, 8 142A-3692-1300 120 V
Series 142 Series 142 Line Voltage Input Temp Range Output Set Point Mounting Retrofit See Notes Below Control Mode Action Heat 3A Relay Fixed Potted CF C4LH 0300 AAAA A Fixed Potted LF E4KU 0572 AAAA A 6, 8 6, 8 142A-3695-1400 120 VAC K t/c 300°C On/Off 142A-3695-2200 230 VAC K t/c 572°F High limit Manual Reset 3A Relay 6, 8 142A-3695-2200 230 VAC K t/c 300°C High limit Manual Reset 3A Relay Fixed Potted LF E4LU 0300 AAAA A 142A-3695-2300 230 VAC K t/c 572°F Hi
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Heat Output Retrofit See Notes Below Set Point Mounting 3A Relay Fixed Potted CF E4HH 0425 AAAA A Fixed Potted CF E4JH 0218 AAAA A 6, 8 142A-3699-2400 230 VAC J t/c 425°F On/Off 142A-3699-2400 230 VAC J t/c 218°C On/Off Heat 3A Relay 6, 8 142A-3700-1200 120 VAC K t/c 200°F High limit Manual Reset 3A Relay Fixed Potted LF C4KU 0200 AAAA A 6, 8 142A-3700-1200 120 VAC K t/c 93°C High limit Ma
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action 142A-3704-1300 120 VAC J t/c 241°C High limit Automatic Reset 3A Relay Fixed Potted LF C4JW 0241 AAAA A 6, 8 142A-3704-1400 120 VAC J t/c 465°F On/Off Heat 3A Relay Fixed Potted CF C4HH 0465 AAAA A 6, 8 142A-3704-1400 120 VAC J t/c 241°C On/Off Heat 3A Relay Fixed Potted CF C4JH 0241 AAAA A 6, 8 Output Set Point Mounting Retrofit See Notes Below 142A-3704-2200 230 VAC J t/c 465°F High limi
Series 142 Series 142 Line Voltage Input 142A-3709-2300 230 VAC K t/c 142A-3709-2300 230 VAC K t/c 142A-3709-2400 230 VAC K t/c 975°F 142A-3709-2400 230 VAC K t/c 524°C On/Off Heat 3A Relay Fixed Potted CF E4LH 0524 AAAA A 6, 8 142A-3710-1200 120 VAC T t/c 482°F High limit Manual Reset 3A Relay Fixed Potted LF C4MU 0482 AAAA A 6, 8 6, 8 Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 975°F High limit Automatic Reset 3A Relay Fi
Series 142 Series 142 Line Voltage Retrofit See Notes Below Input Temp Range Control Mode Action Output Set Point Mounting Manual Reset 3A Relay Fixed Potted LF C4NU 0200 AAAA A Automatic Reset 3A Relay Fixed Potted LF C4MW 0392 AAAA A 6, 8 Automatic Reset 3A Relay Fixed Potted LF C4NW 0200 AAAA A 6, 8 142A-3713-1200 120 VAC T t/c 200°C High limit 142A-3713-1300 120 VAC T t/c 392°F High limit 6, 8 142A-3713-1300 120 VAC T t/c 200°C High limit 142A-3713-1400 120 V
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3716-2200 230 VAC K t/c 122°F High limit Manual Reset 3A Relay Fixed Potted LF E4KU 0122 AAAA A 6, 8 142A-3716-2200 230 VAC K t/c 50°C High limit Manual Reset 3A Relay Fixed Potted LF E4LU 0050 AAAA A 6, 8 142A-3716-2300 230 VAC K t/c 122°F High limit Automatic Reset 3A Relay Fixed Potted LF E4KW 0122 AAAA A 6, 8 142A-3716-2300 230 VAC
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below 142A-3719-2400 230 VAC J t/c 110°C On/Off Heat 3A Relay Fixed Potted CF E4JH 0110 AAAA A 6, 8 142A-3721-1200 120 VAC J t/c 100°F High limit Manual Reset 3A Relay Fixed Potted LF C4HU 0100 AAAA A 6, 8 142A-3721-1200 120 VAC J t/c 38°C High limit Manual Reset 3A Relay Fixed Potted LF C4JU 0038 AAAA A 6, 8 142A-3721-1300 120 VAC J t/c 100°F H
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Heat Output Retrofit See Notes Below Set Point Mounting 3A Relay Fixed Potted CF C4HH 0160 AAAA A Fixed Potted CF C4JH 0071 AAAA A 6, 8 142A-3724-1400 120 VAC J t/c 160°F On/Off 142A-3724-1400 120 VAC J t/c 71°C On/Off Heat 3A Relay 6, 8 142A-3724-2200 230 VAC J t/c 160°F High limit Manual Reset 3A Relay Fixed Potted LF E4HU 0160 AAAA A 6, 8 142A-3724-2200 230 VAC J t/c 71°C High limit Man
Series 142 Series 142 Line Voltage Input 142A-3727-2300 230 VAC 142A-3727-2400 230 VAC 142A-3727-2400 230 VAC Output Set Point Mounting Retrofit See Notes Below Temp Range Control Mode Action J t/c 70°C High limit Automatic Reset 3A Relay Fixed Potted LF E4JW 0070 AAAA A 6, 8 J t/c 158°F On/Off Heat 3A Relay Fixed Potted CF E4HH 0158 AAAA A 6, 8 J t/c 70°C On/Off Heat 3A Relay Fixed Potted CF E4JH 0070 AAAA A 6, 8 142A-3728-1200 120 VAC K t/c 350°F High limit
Series 142 Series 142 Line Voltage Input 142A-3731-1300 120 VAC K t/c 142A-3731-1300 120 VAC K t/c 142A-3731-1400 120 VAC K t/c 950°F Temp Range Retrofit See Notes Below Control Mode Action Output Set Point Mounting 950°F High limit Automatic Reset 3A Relay Fixed Potted LF C4KW 0950 AAAA A 6, 8 510°C High limit Automatic Reset 3A Relay Fixed Potted LF C4LW 0510 AAAA A 6, 8 On/Off Heat 3A Relay Fixed Potted CF C4KH 0950 AAAA A 6, 8 6, 8 142A-3731-1400 120 VAC K t
Series 142 Series 142 Line Voltage Input Temp Range Control Mode Action Output Set Point Mounting Retrofit See Notes Below Note 8: Retrofit controller does not have dual dial scale. Note 9: Hardware lockout is not available on retrofit. Note 10: Retrofit controller does not have user selectable line voltage. Note 11: Retrofit does not support remote set point or retransmit. If wires are on these pins, select a different retrofit.
Series 142 General Description The Watlow Series 142 is a compact, environmentally protected safety limit temperature controller. The limit has a single thermocouple input and is available in several common ranges. User’s Manual The 142 has a single mechanical relay output, and operates as a high limit, latching control with manual and/or auto-power reset. Fixed set points are available.
Units With Remote Setpot Assembly Installation 1.38 in. (35mm) 2.76 in. (70mm) 1. Drill two 2.0 in. (51mm) diameter holes in the desired remote setpot assembly location. See Figure 2b. 1.38 in. (35mm) 1.13 in. (29mm) 2. Using the dial scale as a location template, center and mark all four mounting holes on the dial scale with a center punch. 3. For bolted dial scale assembly, drill four 0.125 in. (3mm) diameter clearance holes. If you are using a screw assembly, use a tap drill.
Wiring P3 Thermocouple + NOTE: All terminals are 1/4 in. (4mm) quick connects. P2 Thermocouple P1 P3 Thermocouple + Reset P2 Thermocouple - Temperature Control Output P1 External Load L2 N.O. L2 Reset N.O. L2 Neutral 120V~ N.C. COM L1 L1 COM N.C. L1 Fuse Fuse Hot Figure 3d — 3A mechanical relay wiring. P3 Figure 3a — 120V~ power wiring (142A - _ _ _ _ - 1 _ 00). Thermocouple + P2 Thermocouple - Red P1 P3 Thermocouple + P2 Reset Thermocouple P1 N.O. L2 Reset L2 N.C.
System Wiring Example L2 L1 21 22 Earth Ground 11 12 N.O. 13 COM L1 Load Power Fuses (+) 9 Indicator turns on when limit trips 10 (-) 988A-2BA0-0000 Rear View N.C. N.O. COM Series 142 142A - 3 _ _ _ - 1200 Safety Limit Control High Limit Mechanical Contactor L2 Load Power N.O. Heat Load Limit Power Process Sensor L1 L2 Thermocouple - + Fuse Momentary Switch Manual Reset for Limit Control Limit Sensor Figure 4 — System wiring example.
Specifications (1599) Limit Control Mode • High limit control • Latched manual reset with ±3°F (1.7°C) hysteresis • Can only be reset when process temperature drops below limit set point. Terminals are provided for remote reset in the event of an overtemperature condition. (Reset switch supplied by user.
Ordering Information (1817) To order, complete the code number 142A-____-__00 to the right with the information below: Series 142 = Temperature safety limit, limit, latching 3A relay, environmentally sealed controller, or basic on-off temperature controller Output Type A = Electromechanical relay1, Form C, 3A, with RC suppression on on-off temperature controller, without contact suppression on limit controller Set Point 2 = Remote/Adjustable2 3 = Fixed (See below for available factory-fixed set points) I
Glossary automatic power reset — A feature in latching limit controllers that does not recognize power outage as a limit condition. When power is restored, the output is re-energized automatically, as long as the temperature is within limits. electrical noise immunity — Ability of a temperature control to operate normally in the presence of electrical noise interference. fixed set point — Temperature set point is preset at the factory. It cannot be readjusted in the field.
Declaration of Conformity Series 142 Watlow Controls 1241 Bundy Blvd.