- Relay Interface Board User’s Guide Watlow Controls 1241 Bundy Blvd. Winona, MN 55987 Customer Service Phone: (800) 414-4299 Fax: (800) 445-8992 Technical Support Phone: (507) 494-5656 Fax: (507) 452-4507 Email: wintechsupport@watlow.com Doc. No. 22822-00. Revision 2. 
- Warranty Watlow Anafaze, Incorporated warrants that the products furnished under this Agreement will be free from defects in material and workmanship for a period of three years from the date of shipment. The customer shall provide notice of any defect to Watlow Anafaze, Incorporated within one week after the Customer's discovery of such defect. 
- If replacement parts are supplied or repairs made during the original warranty period, the warranty period for the replacement or repaired part shall terminate with the termination of the warranty period of the original product or part. The foregoing warranty constitutes the sole liability of Watlow Anafaze, Incorporated and the customer's sole remedy with respect to the products. It is in lieu of all other warranties, liabilities, and remedies. Except as thus provided, Watlow Anafaze, Inc. 
- Relay Interface Board Installation Guide Relay Interface Board Installation Guide Introduction The Relay Interface Board (RIB) replaces the standard I/O terminal board. It connects a Watlow Anafaze controller to a third-party I/O board with 8, 16, 24, or 32 relays. This document lists system requirements, specifications and explains how to install and wire the RIB. 
- Relay Interface Board Installation Guide System Requirements Choose which of the controller’s digital inputs and outputs are needed. Refer to Table 3 and 4 for connections for 24-module I/O boards or Table 5 for connections for a 32-module I/O board. An 8-module I/O board contains the first eight modules of the 24-module board, a 16-module board contains the first 16 modules of the 24module board, etc. • 8, 16 and 24-module I/O boards are connected to J2 and J3 on the RIB. 
- Relay Interface Board Installation Guide Hardware Requirements Choose I/O modules designed to operate with +5 Vdc power. Watlow Anafaze systems are designed to operate at this voltage. Choose I/O boards which have 50-pin headers with long latch levers. Short latch levers will not Watlow Anafaze cables. Calculate the maximum current requirement of the desired I/O boards. If they require more current than the controller can supply, use an external power supply. 
- Relay Interface Board Installation Guide Installation These instructions assume the controller has previously been installed. Tools Needed Mounting 4 Four, #6 screws Screwdriver 1. Choose a mounting location large enough to accommodate the RIB, the I/O board or boards, the ribbon cable or cables and wires that connect them. 2. 
- Relay Interface Board Installation Guide 6.25" (159 mm) 5.75" (145 mm) 3.0" (76 mm) 3. 
- Relay Interface Board Installation Guide Wiring These instructions explain how to connect the RIB to the Watlow Anafaze Controller and to the I/O board. Ribbon Cable Connect the ribbon cable to the controller. Plug the other end of the ribbon cable into the header labeled J1 on the Relay Interface Board. The red stripe on the ribbon cable should line up with Pin 1 on the board. Plug one end of the I/O board ribbon cable into the I/O board and the other end into the RIB. 
- Relay Interface Board Installation Guide Power Connections Choose one of the following options for installing and configuring the jumper on JU1 appropriately for your I/O board. • Option 1: 8, 16, and 24-module I/O boards only: Jumper JU1 in position A to get power from the controller to the I/O boards via the ribbon cable. • Option 2: 8, 16 and 24-module I/O boards only: Jumper JU1 in position B to disconnect the controller power supply. Jumper the I/O boards to get power from the ribbon cable. 
- Relay Interface Board Installation Guide Additional Terminals The Relay Interface Board contains a 5-pin terminal block (TB1) with these functions: TABLE 1. TB1 Functions TB1 Function 1 +5 Vdc power 2 Power common 3 Global alarm output 4 CPU Watchdog output 5 Pulse input These terminals are directly connected to the controller. They allow connection to separate sensors, SSRs, PLCs and safety controls. Jumpers The RIB has three sets of jumpers: JU1, JU2 and JU3. 
- Relay Interface Board Installation Guide TABLE 2. Jumper Positions Jumper Jumper Position A Jumper Position B JU1 Controller supplies +5 Vdc to power both 24-module I/O boards. TB1 terminal 1 can supply power to a 32-module I/O board. Controller power supply is disconnected. TB1 terminal 1 can connect +5 Vdc power from an external supply to both 24-module I/O boards. JU2 Module 3 (on the I/O board connected to connector J2) is connected to the controller’s digital input 1. 
- Relay Interface Board Installation Guide Applying Power After wiring the I/O board modules and selecting the appropriate jumper positions, power may be connected to the system. If power is present at the RIB, the green LED labeled RLY PWR will light. Testing Your System Test the system after connecting power. For specific information on testing controllers, refer to your controller manual. • To test a PID control output, set the appropriate loop to Manual mode and set the output to 100%. 
- Relay Interface Board Installation Guide Controller Connections Tables 3, 4 and 5 describe connections for Watlow Anafaze controllers with the RIB. TABLE 3. 
- Relay Interface Board Installation Guide TABLE 3. 
- Relay Interface Board Installation Guide TABLE 3. 
- Relay Interface Board Installation Guide TABLE 4. 
- Relay Interface Board Installation Guide TABLE 4. 
- Relay Interface Board Installation Guide TABLE 5. 
- Relay Interface Board Installation Guide Module # Controller Function CLS204-4CLS CLS208-8CLS CLS216-16CLS MLS316-16MLS MLS332-32MLS 17 Dig Out 18 Dig Out 18 Loop 2 Cool Pulse Loop Cool Loop 2 Cool Loop 18 Heat/ Loop 2 Cool 18 Dig Out 19 Dig Out 19 Dig Out 19 Loop 2 Cool Loop 3 Cool Loop 19 Heat/ Loop 3 Cool 19 Dig Out 20 Dig Out 20 Dig Out 20 Loop 3 Cool Loop 4 Cool Loop 20 Heat/ Loop 4 Cool 20 Dig Out 21 Dig Out 21 Dig Out 21 Loop 4 Cool Loop 5 Cool Loop 21 Heat/ Loop 5 Cool 21 
- Relay Interface Board Installation Guide Module # Controller Function CLS204-4CLS CLS208-8CLS CLS216-16CLS MLS316-16MLS MLS332-32MLS 18 28 Dig Out 29 Dig Out 29 Dig Out 29 Loop 12 Cool Loop 13 Cool Loop 29 Heat/ Loop 13 Cool 29 Dig Out 30 Dig Out 30 Dig Out 30 Loop 13 Cool Loop 14 Cool Loop 30 Heat/ Loop 14 Cool 30 Dig Out 31 Dig Out 31 Dig Out 31 Loop 14 Cool Loop 15 Cool Loop 31 Heat/ Loop 15 Cool 31 Dig Out 32 Dig Out 32 Dig Out 32 Loop 15 Cool Loop 16 Cool Loop 32 Heat/ Loop