Instruction Manual
PPC-2000 User’s Guide Chapter 3: Operating with AnaWin 3
Doc.# 30002-00 Rev 2.3 Watlow Anafaze 133
Select the Dig I/O button to configure or monitor PPC Digital 
I/O parameters. 
I/O names are located in the first column. The I/O names 
identify each I/O point. Names for Processor (PPC-2010) and 
Digital I/O (PPC-204X) modules differ slightly from Digital Out 
(PPC-206X) and Digital In (PPC-207X) names. Processor and 
Digital I/O names include an I/O type designator because those 
modules support digital, count, and frequency types. For 
example, a Processor I/O name, PPC1:Proc 0.0.2 indicates PPC 
#1, digital I/O on the processor module (which has module 
address 0), I/O type (0=digital) and point #2. See Figure 3.21 for 
a breakdown of this example. Alternatively, the Digital Out 
I/O name, PPC1:DO 41.2 indicates PPC #1, Digital Out module 
with address 41, and point #2. See Figure 3.22 for a breakdown 
of the example. See Table 3.17 on page 134 for module type 
abbreviations.
See Table 2.10 on page 39 for a list of module I/O numbers 
corresponding to the TB50 terminals.
Figure 3.21 PPC-2010 and PPC-204X Digital I/O 
Names
Figure 3.22 PPC-206X and PPC-207X Digital I/O 
Names
PPC1:Proc 0.0.2 
module address
controller number
module type
module I/O number
I/O type
PPC1: DO 41.2 
module address
controller number
module type
module I/O number