A.8 Watlow Power Series Appendix
1 Unit Serial Number High Digits
2 Unit Serial Number Low Digits
4 Software Version
5 Manufactured Date (yymm)
7 Hardware Version
30 Software Build Number
50 Unit Current Rating (Amps)
51 Unit Voltage Rating (Volts)
52 Number Zones Configured
53 Hardware Configured Type
54 Configuration Installed Options
55 Power Control Algorithm Select
56 Fixed Time Base (Sec)
57 Factory Safety Shutdown Temp
58 Load Type Select (Control Zone 1 only,
3 Phase only.)
80 Voltage Compensation (On/Off)
85 Comms Watchdog Select (On/Off)
86 Comms Watchdog Timeout (S)
87 Comms Watchdog Failure Output Power
Select
150 Analog (mA) Input 1 Signal
151 Analog (V) Input 1 Signal
152 Line Potential (Volts) rms Line 1
153 A/D Counts Input 1
154 Load Current (Amps) rms Line 1
155 Single Phase 0.1 kVA Zone 1
156 Load Power (kVA) Zone 1
157 Heater Bakeout Timeout Zone 1
159 Output 1 Power (%)
160 Analog (mA) Input 2 Signal
161 Analog (V) Input 2 Signal
162 Line Potential (Volts) rms Line 2
163 A/D Counts Input 2
164 Load Current (Amps) rms Line 2
165 0.1 kVA Zone 2
166 Load Power (kVA) Zone 2
167 Heater Bakeout Timeout Zone 2
169 Output 2 Power (%)
170 Analog (mA) Input 3 Signal
171 Analog (V) Input 3 Signal
172 Line Potential (Volts) rms Line 3
173 A/D Counts Input 3
174 Load Current (Amps) rms Line 3
175 0.1 kVA Zone 3
176 Load Power (kVA) Zone 3
177 Heater Bakeout Timeout Zone 3
179 Output 3 Power (%)
180 Active Alarms
181 Heater Open alarm
182 Heater Tolerance Alarm
183 Heat Sink Over Temperature Alarm
184 Line Loss Alarm
185 Phase Balance Alarm
186 Load Balance Alarm
187 Frequency Out of Tolerance Alarm
188 Line Compensation Alarm
189 Line Over Voltage Alarm
190 Communications Watchdog Alarm
195 Active Errors
198 Line Frequency (Hz)
850 Active Relay State
851 Global Alarm Configuration
860 Heater Open Alarm Config.
861 Heater Tolerance Alarm Config.
862 Over Temperature Alarm Config.
863 Line Loss Alarm Configuration
864 Phase Balance Alarm Config.
865 Load Balance Alarm Config.
866 Frequency Out of Tolerance Alarm
Configuration
867 Voltage Compensation Alarm Config.
868 Over Voltage Alarm Config.
869 Comms Watchdog Alarm Configuration
870 Retransmit Config. Select
871 Retransmit Type Select
872 Retransmit Phase Select
873 Retransmit Zone Select
876 Minimum Amps Retransmit
877 Maximum Amps Retransmit
878 Minimum kVA Retransmit
879 Maximum kVA Retransmit
880 Set Retransmit Output Low Voltage (Volts)
881 Set Retransmit Output High Voltage (Volts)
882 Set Retransmit Output Low Current (mA)
883 Set Retransmit Output High Current (mA)
950 Restore Data Set
951 Backup Data Set
952 Default Data Set
959 Enable NVOL Storage
990 Heat Sink Alarm Temp
991 Load Balance Percentage
1350 Global Lockout
1351 Control Setup Menus Lockout
1352 Options Setup Menus Lockout
1353 Alarms Setup Menu Lockout
1354 Comms Setup Menu Lockout
1355 Retransmit Setup Menu Lockout
1356 Analog Input Factory Menus Lockout
1357 Retransmit Cal Factory Menu Lockout
1358 System Data Factory Menu Lockout
1359 Diagnostics Factory Menu Lockout
1513 Display Test
1540 Line Loss Alarm, Most Recent Type, Line 1
1541 Line Loss Alarm, Previous Type, Line 1
1542 Line Loss Alarm, Least Recent Type, Line 1
1543 Line Loss Alarm, Most Recent Type, Line 2
1544 Line Loss Alarm, Previous Type, Line 2
1545 Line Loss Alarm, Least Recent Type, Line 2
1546 Line Loss Alarm, Most Recent Type, Line 3
1547 Line Loss Alarm, Previous Type, Line 3
1548 Line Loss Alarm, Least Recent Type, Line 3
1555 Retransmit Set Test Word
1560 to 1573 Read Selected A/D Counts
1580 Select Discrete Input
1581 Read Selected Input Value
1590 Heat Sink Temp (°C)
1591 Record High Heat Sink Temp
1700 Factory Mode Request
1799 Factory Password Entry
1960 Accum Hours (10K - 100M)
1961 Accum Hours (0 - 9999)
5011 Set Analog Input Low Current Scale (mA)
Zone 1
5012 Set Analog Input High Current Scale (mA)
Zone 1
5013 Set Analog Input Low Voltage Scale (Volts)
Zone 1
5014 Set Analog Input High Voltage Scale (Volts)
Zone 1
5019 Learn Input Request (Hi, Lo) Zone 1
5021 Set Analog Input Low Current Scale (mA)
Zone 2
5022 Set Analog Input High Current Scale (mA)
Zone 2
5023 Set Analog Input Low Voltage Scale (Volts)
Zone 2
5024 Set Analog Input High Voltage Scale (Volts)
Zone 2
5029 Learn Input Request (Hi, Lo) Zone 2
5031 Set Analog Input Low Current Scale (mA)
Zone 3
5032 Set Analog Input High Current Scale (mA)
Zone 3
5033 Set Analog Input Low Voltage Scale (Volts)
Zone 3
5034 Set Analog Input High Voltage Scale (Volts)
Zone 3
5039 Learn Input Request (Hi, Lo) Zone 3
5101 Input Signal Method Select (dig, mA, Volt)
Zone 1
5102 Numeric (%) Input 1 Signal
Modbus Register Numbers
Relative Parameter Numbers (For Absolute Numbers, add 40001 to the Relative Number.)
5103 Default Numeric Input Signal (%)
Zone 1
5104 Maximum Rate of Change (%/100msec)
Zone 1
5105 Soft Start Time (Sec) Zone 1
5106 Inductive Load Factor Request Zone 1
5107 Inductive Load Current Zone 1
5110 Heater Bakeout Select (On/Off) Zone 1
5111 Heater Bakeout Select Time Zone 1
5112 Current Limit Select (On/Off) Zone 1
5113 Current Limit Set Point (A) Zone 1
5114 Low Tolerance Set Point (A) Zone 1
5115 High Tolerance Set Point (A) Zone 1
5116 Heater Bakeout Overcurrent Trip Zone 1
5201 Input Signal Method Select (dig, mA,
Volt) Zone 2
5202 Numeric (%) Input 2 Signal
5203 Default Numeric Input Signal (%)
Zone 2
5204 Maximum Rate of Change (%/100msec)
Zone 2
5205 Soft Start Time (Sec) Zone 2
5206 Inductive Load Factor Request Zone 2
5207 Inductive Load Current Zone 2
5210 Heater Bakeout Select (On/Off) Zone 2
5211 Heater Bakeout Select Time Zone 2
5212 Current Limit Select (On/Off) Zone 2
5213 Current Limit Set Point (A) Zone 2
5214 Low Tolerance Set Point (A) Zone 2
5215 High Tolerance Set Point (A) Zone 2
5216 Heater Bakeout Overcurrent Trip Zone 2
5301 Input Signal Method Select (dig, mA,
Volt) Zone 3
5302 Numeric (%) Input 3 Signal
5303 Default Numeric Input Signal (%)
Zone 3
5304 Maximum Rate of Change (%/100msec)
Zone 3
5305 Soft Start Time (Sec) Zone 3
5306 Inductive Load Factor Request Zone 3
5307 Inductive Load Current Zone 3
5310 Heater Bakeout Select (On/Off) Zone 3
5311 Heater Bakeout Select Time Zone 3
5312 Current Limit Select (On/Off) Zone 3
5313 Current Limit Set Point (A) Zone 3
5314 Low Tolerance Set Point (A) Zone 3
5315 High Tolerance Set Point (A) Zone 3
5316 Heater Bakeout Overcurrent Trip Zone 3
5411 Adjust Low mA Cal Point Zone 1
5412 Adjust High mA Cal Point Zone 1
5413 Adjust Low V Cal Point Zone 1
5414 Adjust High V Cal Point Zone 1
5415 Calibrate Analog Input Request Zone 1
5421 Adjust Low mA Cal Point Zone 2
5422 Adjust High mA Cal Point Zone 2
5423 Adjust Low V Cal Point Zone 2
5424 Adjust High V Cal Point Zone 2
5425 Calibrate Analog Input Request Zone 2
5431 Adjust Low mA Cal Point Zone 3
5432 Adjust High mA Cal Point Zone 3
5433 Adjust Low V Cal Point Zone 3
5434 Adjust High V Cal Point Zone 3
5435 Calibrate Analog Input Request Zone 3
5591 Baseline Voltage Learn Request Zone 1
5592 Baseline Voltage Learn Request Zone 2
5593 Baseline Voltage Learn Request Zone 3
5594 Baseline Voltage Read/Adjust Zone 1
5595 Baseline Voltage Read/Adjust Zone 2
5596 Baseline Voltage Read/Adjust Zone 3
5700 Cal Retransmit Request
5710 Retransmit Cal mA Low
5711 Retransmit Cal mA High
5720 Retransmit Cal Volts Low
5721 Retransmit Cal Volts High