User guide

Appendix Watlow Power Series A.3
All Units (continued)
Single Phase Units
Multizone Units
3 Phase, 2-Leg Units
3 Phase, 3-Leg Units
For 3 phase, 3 grounded wye models only, reference
connections must be connected to neutral. (See page
3.5 for wiring.)
In the Setup Page, Setup Control Zone 1 menu,
select the load type for Zone 1.
Reference is not connected for 3 phase, 3-
leg grounded wye unit.
Load Type Select [type] for 3 phase is
set to unconfigured [none].
No Heat
Corrective ActionProbable CauseIndication
If power is not routed through or connected to the
internal bussbar, Ref. 1 or 3 (not both) must be
connected to middle line. (See page 3.4 for wiring.)
In the Setup Page, Setup Control Zone 1 menu,
select the load type for Zone 1.
Power not routed through the internal
bussbar. Controller will indicate [`alr]
(Line Loss Alarm) [line].
Load Type Select [type] for 3 phase is
set to unconfigured [none].
No Heat
Corrective ActionProbable CauseIndication
When using the multizone feature, the 2 or 3 zones
should be wired so that no two phases are 180° out
of phase. See wiring diagram page 3.5, Figure 3.5C.
Two phases are 180° out of phase of each
other.
No current
monitor on the
display.
Reference connections to other lines or neutral must
be made appropriately for each zone. (See page 3.5
for wiring.)
Reference not connected.No Heat
Corrective ActionProbable CauseIndication
If power is not routed through or connected to the
internal bussbar, Ref. 2 must be connected to another
line or to neutral. (See page 3.4 for wiring.)
Power not routed through the internal
bussbar. Controller will indicate [`alr]
(Line Loss Alarm) [line].
No Heat
Corrective ActionProbable CauseIndication
Refer to page 2.1; insure the fuses have the correct
current rating.
Refer to page A.6 for guidelines on proper torquing of
fuses.
Refer to page 2.3 for enclosure guidelines and how to
determine how much cooling is required.
Replace heater.
Improper fuse current rating.
Fuses improperly torqued.
Inadequate ventilation or cooling in the
cabinet.
Intermittent short in heater.
Frequent
Nuisance Fuse
Blowing
Corrective ActionProbable CauseIndication
Phase angle
control ramps
output power
up, develops a
[hCyL] error
and shuts down
Inductive load causing half cycle line
loss errors [hCYL] . Reactance delay
[rdLy] is set too low.
Increase [rdLy] value until the half cycle line loss
errors no longer occur..