User guide
Active if [glOC] is set to [`Unl].
Active if retransmit and heater
diagnostics options are
installed.
1357 r/w 
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
[C| rtr] Retransmit Cal
Factory Menu
Lockout
Sets lock on retrans-
mit calibration
menu.
Active if [glOC] is set to [`Unl].
1356 r/w 
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{`CIn} Analog Input Fac-
tory Menus Lock-
out
Sets lock on input
calibration menu.
Active if [glOC] is set to [`Unl].
Active if retransmit and heater
diagnostics options are
installed.
1355 r/w 
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{retr} Retransmit Setup
Menu Lockout
Sets lock on retrans-
mit menu.
Active if [glOC] is set to [`Unl].
Active if serial communications
option is installed.
1354 r/w 
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{COM} Comms Setup
Menu Lockout
Sets lock on commu-
nications menu.
Active if [glOC] is set to [`Unl].
1353 r/w 
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{`Alr} Alarms Setup
Menu Lockout
Sets lock on alarm
configuration menu.
Active if [glOC] is set to [`Unl].
Active if heater diagnostics
option is installed.
1352 r/w
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{`Opt} Options Setup
Menus Lockout
Sets lock on all
options setup menus.
Active if [glOC] is set to [`Unl].
1351 r/w
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
[`Ctr] Control Setup
Menus Lockout
Sets lock on all
control setup menus.
Active: Always.1350 r/w
[`Unl] (0)[`Unl] Unlocked (0)
[`LOC] Locked (1)
{gLOC} Global Lockout
Sets the state of
global lockout which
allows all prompts to
be write protected. If
set to unlocked, indi-
vidual menu locks
can be set.
[`LOC] Global/Menu Lockouts Menu
[Fcty] Factory Page
This menu is used to set the lockout parameters. Locked means that the parameters in the menu
cannot be changed.
Active: Always.959 r/w
[``On] (0)[``On] enable (0)
[`OFF] disable (1)
[nUOL] Enable NVOL
Storage
Enable/disable non-
volatile memory.
6.16 ■ Watlow Power Series Parameters, Chapter 6
Display Parameter Range Default Modbus Conditions for 
(Modbus Value) Address Parameters to Appear
read/write