User guide

Active if [glbl] is set to [`Off].
863 r/w
[`std]
active (0)
[`std] active (0)
[`LaT] latched (1)
[`SIl] silenced (2)
[LaSI] latched and
silenced (3)
[Line] Line Loss Alarm
Configuration
Selects the line loss
alarm configuration.
Active: Always.
Output will de-energize at this
heatsink shut down tempera-
ture (degrees C). The default
maximum temperature is
model number dependent.
990 r/w Value equal to
[`sdÇ] or
less. User
adjustable.
See Factory
Menu for
actual safety
shutdown
temp.
[```0] to [`sdÇ] [alÇ`] Heat Sink Over
Temperature Alarm
Temperature
Select heat sink
overtemp alarm
configuration.
Active if [glbl] is set to [`Off].
862 r/w
[`std]
active (0)
[`std] active (0)
[`LaT] latched (1)
[`SIl] silenced (2)
[LaSI] latched and
silenced (3)
[``OT] Heat Sink Over
Temperature
Alarm Config.
Select over tempera-
ture alarm configu-
ration.
Active if heater diagnostics is
installed.
Active if [glbl] is set to [`Off].
861 r/w
[`std]
active (0)
[`std] active (0)
[`LaT] latched (1)
[`SIl] silenced (2)
[LaSI] latched and
silenced (3)
[`tol] Heater Tolerance
Alarm Config.
Selects heater
tolerance alarm
configuration.
Active if heater diagnostics is
installed.
Active if [glbl] is set to [`Off].
860 r/w
[`std]
active (0)
[`std] active (0)
[`LaT] latched (1)
[`SIl] silenced (2)
[LaSI] latched and
silenced (3)
[Open] Heater Open
Alarm Config.
Select heater open
alarm configuration.
Active: Always.851 r/w
[`std] all
alarms
active (0)
[`std] all alarms
active (0)
[`LaT] latched (1)
[`SIl] silenced (2)
[LaSI] latched and
silenced (3)
[`Off] off (4)
[glbl] Global Alarm
Configuration
Selects global alarm
configuration. Config-
ures all alarms to the
same type or if set to
OFF allows individual
alarm configuration.
Active: Always.
850 r/w
[al`O] de-
energized
on alarm
(1)
[al`C] energized on
alarm (0)
[al`O] de-energized
on alarm (1)
[a| lgc] Active Relay State
Select the relay
state on an alarm
condition.
[`Alr] Setup Alarms Configuration Menu
[`Set] Setup Page
This menu is used to set up the alarm configuration. For a definition of the alarm types —
standard, latched, silenced, latched and silenced, see page 5.7.
6.10 Watlow Power Series Parameters, Chapter 6
Display Parameter Range Default Modbus Conditions for
(Modbus Value) Address Parameters to Appear
read/write