Owner's manual
Parameters
5.2 Watlow MicroDIN  =Read Only;  =Read/Write;  =Turn On/Off
ON
System Group continued
System Group – Monitor
System Error 
• See Error Group.
Ambient (CJC) Temperature 
• Read the ambient temperature in 0.1 degrees Fahrenheit.
• Read only 
• Modbus: 1500
Range
0.0 to 180.0 F
Default
none
Active
always
System Group – Use
Non-volatile Memory 
• Disable storage of parameters to non-volatile (EEPROM) memory.
This allows you to change parameters frequently without wearing
out the memory.
• Read/write
• Modbus: 24
Range
0: store parameters when they are changed
1: do not store parameters when they are changed
Default
0 (always reverts to 0 when the controller’s power is turned off
and on)
Active
always
Affects
all parameters
will not save any parameters when set to 1.
ç
CAUTION: 
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
volatile Memory
(System Group).