  ST   •    5   •  Chapter  1 Over view
Getting Started Quickly
The ST control has a page and menu structure that is 
listed below along with a brief description of its pur-
pose.
Setup Page
Push and hold the up 
and down keys (¿ ¯) 
for 6 seconds to enter.  
(See the Setup Page for 
further information)
Once received, a user 
would want to setup 
their control prior to op-
eration. As an example, 
define the input type 
and set the output cycle 
time.
Operations Page
Push and hold the up 
and down keys (¿ ¯) 
for 3 seconds to enter.  
(See the Operations 
Page for further infor-
mation)
After setting up the con-
trol to reflect your equip-
ment, the Operations 
Page would be used 
to monitor or change 
runtime settings. As an 
example, the user may 
want to see how much 
time is left in a profile 
step or perhaps change 
the autotune set point.
Factory Page
Push and hold the In-
finity and the green 
Advance keys (ˆ 
‰
) for 
6 seconds to enter.  (See 
the Factory Page for fur-
ther information)
For the most part the 
Factory Page has no 
bearing on the control 
when running. Here, a 
user may want to enable 
password protection, 
view the control part 
number or perhaps cre-
ate a custom Home Page.
Profile Page
Push and hold the the 
green Advance key 
‰
 for 
6 seconds to enter.  (See 
the Profile Page for fur-
ther information)
If equipped with this 
feature, a user would 
want to go here to con-
figure a profile.
The default ST loop configuration out of the box is 
shown below: 
•  Analog Input functions set to thermocouple, type J
• Heat algorithm set for PID, Cool set to off
• Output 1 set to Heat
• Control mode set to Auto
• Set point set to 75 °F
If you are using the input type shown above, simply 
connect your input and output devices to the control. 
Power up the control and push the up arrow ¿ on 
the face of the control to change the set point from 
the default value of 75 °F to the desired value. As the 
Set Point increases above the Process Value, output 1 
will come on and it will now begin driving your output 
device. 
Note:
The output cycle time will have a bearing on the 
life of mechanical relay outputs and can be differ-
ent based on the type of output ordered. The output 
cycle time can be changed in the Setup Page under 
the Output Menu.
EZ-ZONE ST Default Configuration
Thermocouple Type J
Analog Input 1
PID 
Controller
Heat
Loop 1
Input Sensor
Heat
Output
Function
Input
Function
Output 1