Manual
Watlow  EZ-ZONE
®
  ST   •    40    •   Chapter  4 Setup  Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative
Address
CIP
Class 
Instance
Attribute
hex (dec)
Pro DP 
Index
Par
ID
RUI/
GTW 
Mod-
bus
Data 
Type 
& 
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1 to 2) 
Sensor Type 
Set the analog sensor type 
to match the device wired 
to this input.
Note: 
  There is no open-   
sensor detection    
for process inputs.
[`oFF] Off (62)
[``tC] Thermocouple (95) 
[`mu] Millivolts (56) 
[uolT] Volts dc (104)
[`MA]
 Milliamps dc (112) 
[r0;1H] RTD 100 Ω (113) 
[r1;0H] RTD 1,000 Ω (114) 
Instance 1
Map 1  Map 2
42  368
Instance 2
Map 1  Map 2
 70  458
0x68 (104)
1 to 2
5
3 4005 Inst. 1
368
Inst. 2
528
uint
RWES
[`Lin]
[ Lin]
Analog Input (1 to 2) 
Linearization
Set the linearization to 
match the thermocouple 
wired to this input.
[```J] J (46)
[```F] F (30)
[```E] E (26)
[```d] D (23)
[```C] C (15)
[```b] B (11)
[```t] T (93)
[```S] S (84)
[```r] R (80)
[```n] N (58)
[```H] K (48)
J
Instance 1
Map 1  Map 2
43  370
Instance 2
Map 1  Map 2
 71   460
0x68 (104)
1 to 2
6
4 4006 Inst. 1
370
Inst. 2
530
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1 to 2) 
RTD Leads
Set to match the number 
of leads on the RTD wired 
to this input.
[```2] 2 (1)
[```3] 3 (2)
2 Instance 1
Map 1  Map 2
44  372
Instance 2
Map 1  Map 2
 72   462
0x68 (104)
1 to 2
7
- - - - 4007 Inst. 1
372
Inst. 2
532
uint
RWES
[Unit]
[Unit]
Analog Input (1 to 2) 
Units
Set the type of units the 
sensor will measure.
[`A;tP] Absolute Temperature 
(1540)
[``rh] Relative Humidity 
(1538)
[`Pro] Process (75)
[PWr] Power (73)
Process Instance 1
Map 1  Map 2
- - - -  442
Instance 2
Map 1  Map 2
 - - - -  532
0x68 (104)
1 to 2
0x2A (42)
5 4042 - - - - uint
RWES
Note: 
  Some values will be rounded off to fit in the four-character display.
  Full values can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read 
W: Write 
E: EE-
PROM
S: User 
Set
To go to the Setup Page from the Home Page, press both 
the Up ¿ and Down ¯ keys for six seconds. [``Ai] will 
appear in the upper display and [`Set] will appear in 
the lower display.
•  Press the Up ¿ or Down ¯ key to move through 
the menus.
•  Press the Advance Key
‰
to move to a submenu.
•  Press the Up ¿ or Down ¯ key to move through 
the submenus.
•  Press the Advance Key
‰
to move through the pa-
rameters of the menu or submenu.
•  Press the Infinity Key ˆ to move backwards 
through the levels: parameter to submenu; sub-
menu to menu; menu to Home Page.
•  Press and hold the Infinity Key ˆ for two seconds 
to return to the Home Page.
Note: 
  Avoid continuous writes within loops. Excessive writes to EEPROM  
  will cause premature EEPROM failure. The EEPROM is rated for    
  1,000,000 writes. Navigate to Setup Page under the CoM menu and   
  set prompt Non-volatile Save [`nU;S] to No.