User guide

Watlow EZ-ZONE
®
RMH Module 92 Chapter 4 Setup Page
RM High Density Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[`FiL]
[ FiL]
Math (1 to 24)
Filter
Filtering smooths out the
output signal of this func-
tion block. Increase the
time to increase filtering.
0.0 to 60.0 seconds 0.0 6594
[offset 70]
0x7D
(125)
1 to 24
0x1C (28)
- - - - 25028 float
RWES
[`uAr]
[`Set]
Variable Menu
[tyPE]
[tyPE]
Variable (1 to 24)
Data Type
Set the variable's data
type.
[AnLg] Analog (1215)
[`Dig] Digital (1220)
Analog 16060
[offset 20]
0x66 (102)
1 to 24
1
152 2001 uint
RWES
[Unit]
[Unit]
Variable (1 to 24)
Units
Set the variable's units.
[`A;tp] Absolute Temperature
(1540)
[`r;tp] Relative Temperature
(1541)
[PWr] Power (73)
[`Pro] Process (75)
[``rh] Relative Humidity
(1538)
[nonE] None (61)
Absolute
Temper-
ature
16072
[offset 20]
0x66 (102)
1 to 24
7
- - - - 2007 uint
RWES
[`Dig]
[ dig]
Variable (1 to 24)
Digital
Set the variable's value.
[`oFF] Off (62)
[``on] On (63)
Off 16062
[offset 20]
0x66 (102)
1 to 24
2
153 2002 uint
RWES
[anLg]
[AnLg]
Variable (1 to 24)
Analog
Set the variable's value.
-1,999.000 to 9,999.000
Note:
Stored in °F only
0.0 16064
[offset 20]
0x66 (102)
1 to 24
3
212 2003 float
RWES
No Dis-
play
Variable (1 to 24)
Output Value
Off (62)
On (63)
-1,999.000 to 9,999.000
- - - - 16066
[offset 20]
0x66 (102)
1 to 24
4
- - - - 2004 float
R
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global
Display Units
Select which scale to use
for temperature.
[```F] °F (30)
[```C] °C (15)
°F 368 0x67 (103)
1
5
85 3005
uint
RWES
[AC;LF]
[AC.LF]
Global
AC Line Frequency
Set the frequency to the ap-
plied ac line power source.
[``50] 50 Hz (3)
[``60] 60 Hz (4)
60 Hz - - - - 0x65 (101)
1
0x22 (34)
- - - - 1034 uint
RWES
[d;prs]
[dPrS]
Global
Display Pairs
Defines the number of
display pairs at the home
page of an RUI
1 to 25 2 - - - - 0x67 (103)
1
0x1C (28)
- - - - 3028 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User
Set