User guide
Watlow EZ-ZONE
®
 RMH Module  • 66 •  Chapter 4 Setup Page
  RM High Density Module  •  Setup Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& 
Read/
Write
[`o;Ct] 
[ o.Ct]
Output Digital (1 to 12) 
Control
Set the output control type. 
This parameter is only 
used with PID control, but 
can be set anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base 
(103)
Fixed 
Time 
Base
1822
[offset 30]
0x6A 
(106)
1 to 12
2
75 6002 uint
RWES
[`o;tb]
[ o.tb]
Output Digital (1 to 12) 
Time Base
Set the time base for fixed-
time-base control.
0.1 to 60.0 seconds (solid-
state relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or no-arc power 
control)
0.1 sec. 
[SSR & 
sw dc]
20.0 sec. 
[mech, 
relay, no-
arc]
1824
[offset 30]
0x6A 
(106)
1 to 12
3
76 6003 float
RWES
[`o;Lo]
[ o.Lo]
Output Digital (1 to 12) 
Low Power Scale
The power output will nev-
er be less than the value 
specified and will represent 
the value at which output 
scaling begins.
0.0 to 100.0% 0.0% 1836
[offset 30]
0x6A 
(106)
1 to 12
9
77 6009 float
RWES
[`o;hi]
[ o.hi]
Output Digital (1 to 12) 
High Power Scale
The power output will 
never be greater than the 
value specified and will 
represent the value at 
which output scaling stops.
0.0 to 100.0% 100.0% 1838
[offset 30]
0x6A 
(106)
1 to 12
0xA (10)
78 6010 float
RWES
[`o;ty]
[ o.ty]
Output Process (1 to 3, 7 
to 9) 
Type **
Select whether the process 
output will operate in volts 
or milliamps.
[uoLt] Volts (104)
[`MA] Milliamps (112)
Volts 16540
[offset 60]
0x76 (118)
1-3, 7-9
1
- - - - 18001 uint
RWES
Note: 
Some values will be rounded off to fit in the four-character display. 
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and 
above.
R: Read 
W: Write 
E: EEPROM 
S: User 
Set