RMH Module 63 Chapter 4 Setup Page
RM High Density Module Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Probus
Index
Parameter
ID
Data
Type
&
Read/
Write
[FAiL]
[FAiL]
Control Loop (1 to 16)
Input Error Failure
Select what the controller
outputs will do when an
input error switches control
to manual mode.
[`oFF] Off, sets output power
to 0% (62)
[bPLS] Bumpless transfer
maintains same output
power, if it was less than
75% and stable, otherwise
0% (14)
[MAn] Manual power sets
output power to Manual
Power setting (33)
[USEr] User sets output pow-
er to last open-loop set point
the user entered (100)
User 5244
[offset 80]
0x6B
(107)
1 to 16
0xD (13)
- - - - 7013 uint
RWES
[MAn]
[MAn]
Control Loop (1 to 16)
Manual Power
Set the manual output
power level that will take
effect if an input error fail-
ure occurs while User Fail-
ure Action is set to Manual
Power.
Set Point Open Loop Limit
Low to Set Point Open Loop
Limit High (Setup Page)
0.0 5240
[offset 80]
0x6B
(107)
1 to 16
0xB (11)
- - - - 7011 float
RWES
[`L;dE]
[ L.dE]
Control Loop (1 to 16)
Open Loop Detect En-
able
Turn on the open-loop
detect feature to monitor
a closed-loop operation for
the appropriate response.
[``no] No (59)
[`YES} Yes (106)
No 4142
[offset 70]
0x97 (151)
1 to 16
0x16 (22)
64 8039 uint
RWES
[`L;dt]
[ L.dt]
Control Loop (1 to 16)
Open Loop Detect Time
The Open Loop Detect De-
viation value must occur
for this time period to trig-
ger an open-loop error.
0 to 3,600 seconds 240 4144
[offset 70]
0x97 (151)
1 to 16
0x17 (23)
65 8040 uint
RWES
[`L;dd]
[ L.dd]
Control Loop (1 to 16)
Open Loop Detect Devia-
tion
The value entered repre-
sents the Process Value de-
viation that must occur to
trigger an open-loop error.
-1,999.000 to 9,999.000°F or
units
-1,110.555 to 5,555.000°C
10.0°F or
units
6.0°C
4146
[offset 70]
0x97 (151)
1 to 16
0x18 (24)
66 8041 float
RWES
[``rP]
[ rP]
Control Loop (1 to 16)
Ramp Action
Select when the controller's
set point will ramp to the
defined end set point.
[`oFF] Off (62)
[`Str] Startup (88)
[StPt] Set Point Change
(1647)
[both] Both (13)
Off 5246
[offset 80]
0x6B
(107)
1 to 16
0xE (14)
- - - - 7014 uint
RWES
[`r;SC]
[ r.SC]
Control Loop (1 to 16)
Ramp Scale
Select the scale of the ramp
rate.
[hoUr] Hours (39)
[Min] Minutes (57)
Minutes 5248
[offset 80]
0x6B
(107)
1 to 16
0xF (15)
- - - - 7015 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display.
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and
above.
R: Read
W: Write
E: EEPROM
S: User
Set