User guide
Watlow EZ-ZONE
®
 RMH Module  • 59 •  Chapter 4 Setup Page
  RM High Density Module  •  Setup Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& 
Read/
Write
[SFn;A]
[SFn.A]
Action (1 to 24)
Source Function A
Set the event or function 
that will trigger the action.
[nonE] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A 
(233)
[Ent;b] Profile Event Out B 
(234)
[Ent;C] Profile Event Out C 
(235)
[Ent;d] Profile Event Out D 
(236)
[Ent;E] Profile Event Out E 
(247)
[Ent;F] Profile Event Out F 
(248)
[Ent;g] Profile Event Out G 
(249)
[Ent;h] Profile Event Out H 
(250)
[`FUn] Function Key (1001)
[LiM] Limit (126)
[`LgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 2190
[offset 20]
0x6E 
(110)
1 to 24
6
- - - - 10006 uint
RWES
[`Si;A]
[ Si.A]
Action (1 to 24)
Source Instance A
Set the instance of the 
function selected above.
1 to 250 1 2182
[offset 20]
0x6E 
(110)
1 to 24
2
- - - - 10002 uint
RWES
[`S2;A]
[ SZ.A]
Action (1 to 24)
Source Zone A
Set the zone of the function 
selected above.
0 to 16 0 2192
[offset 20]
0x6E 
(110)
1 to 24
7
- - - - 10007 uint
RWES
[`LEu]
[ LEv]
Action (1 to 24)
Active Level
Set the action that will be 
considered a true state.
[LoW] Low (53)
[high] High (37)
High 2180
[offset 20]
0x6E 
(110)
1 to 24
1
112 10001 uint
RWES
[LooP]
[`Set]
Control Loop Menu
[SFn;A]
[SFn.A]
Control Loop (1 to 16)
Source Function A
Set the type of function 
that will be used for this 
source.
[``Ai] Analog Input (142)
[``Pu] Process Value (241)
Analog 
Input
4156
[offset 70]
0x97 (151)
1 to 16
0x1D (29)
- - - - 8050 uint
RWE
Note: 
Some values will be rounded off to fit in the four-character display. 
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and 
above.
R: Read 
W: Write 
E: EEPROM 
S: User 
Set