User guide
Watlow EZ-ZONE
®
 RMH Module  • 55 •  Chapter 4 Setup Page
  RM High Density Module  •  Setup Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& 
Read/
Write
[SFn;E]
[SFn.E]
Process Value (1 to 16)
Source Function E
Set the type of function 
that will be used for this 
source.
[nonE] None (61)
[ALM] Alarm (6)
[`CPE] Compare (230)
[`Ctr] Counter (231)
[`dio] Digital I/O (1142)
[Ent;A] Profile Event Out A 
(233)
[Ent;b] Profile Event Out B 
(234)
[Ent;C] Profile Event Out C 
(235)
[Ent;d] Profile Event Out D 
(236)
[Ent;E] Profile Event Out E 
(247)
[Ent;F] Profile Event Out F 
(248)
[Ent;g] Profile Event Out G 
(249)
[Ent;h] Profile Event Out H 
(250)
[`FUn] Function Key (1001)
[`lgC] Logic (239)
[tMr] Timer (244)
[`uAr] Variable (245)
None 8228
[offset 70]
0x7E 
(126)
1 to 16
5
- - - - 26005 uint
RWES
[`Si;E]
[ Si.E]
Process Value (1 to 16)
Source Instance E
Set the instance of the 
function selected above.
1 to 250 1 8238
[offset 70]
0x7E 
(126)
1 to 16
0x0A (10)
- - - - 26010 uint
RWES
[`s2;E]
[ SZ.E]
Process Value (1 to 16)
Source Zone E
Set the zone of the function 
selected above.
0 to 16 0 8248
[offset 70]
0x7E 
(126)
1 to 16
0x0F (15)
- - - - 26015 uint
RWES
[``C;p]
[ SZ.E]
Process Value (1 to 16)
Cross Over Point
Enter a value where the 
Output Value switches 
from Source A to Source 
B value. This applies only 
when the Process function 
is set to Cross Over.
-1,999.000 to 9,999.000 units 
or °F
-1,128.333 to 5,537.223 °C
100.0 8266
[offset 70]
0x7E 
(126)
1 to 16
0x18 (24)
- - - - 26024 float
RWES
[``C;b]
[ SZ.E]
Process Value (1 to 16)
Cross Over Band
Enter a band centered 
about the Cross Over 
Point where Output Value 
switches from Source A to 
Source B Value. This ap-
plies only when the Process 
function is set to Cross 
Over.
-1,999.000 to 9,999.000 units 
or °F 
-1,128.333 to 5,537.223 °C
10.0 8268
[offset 70]
0x7E 
(126)
1 to 16
0x19 (25)
- - - - 26025 float
RWES
Note: 
Some values will be rounded off to fit in the four-character display. 
Full values can be read with other interfaces.
Note:
If there is only one instance of a menu, no submenus will appear.
** These parameters/prompts are available in these menus with firmware revisions 6.0 and 
above.
R: Read 
W: Write 
E: EEPROM 
S: User 
Set