User guide
Watlow EZ-ZONE
®
 RMH Module  • 47 •  Chapter 3 Operations Page
  RM High Density Module  •  Operations Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& Read/
Write
[`Su;C]
[ Su.C]
Logic (1 to 24)
Source Value C
View the value of Source 
C.
[`off] Off (62)
[``on] On (63)
9392
[offset 80]
0x7F 
(127)
1 to 24
0x1B (27)
- - - - 27027 uint
R
[`Su;d]
[ Su.d]
Logic (1 to 24)
Source Value D
View the value of Source 
D.
[`off] Off (62)
[``on] On (63)
9394
[offset 80]
0x7F 
(127)
1 to 24
0x1C (28)
- - - - 27028 uint
R
[`Su;E]
[ Su.E]
Logic (1 to 24)
Source Value E
View the value of Source 
E.
[`off] Off (62)
[``on] On (63)
9396
[offset 80]
0x7F 
(127)
1 to 24
0x1D (29)
- - - - 27029 uint
R
[`Su;F]
[ Su.F]
Logic (1 to 24)
Source Value F
View the value of Source 
F.
[`off] Off (62)
[``on] On (63)
9398
[offset 80]
0x7F 
(127)
1 to 24
0x1E (30)
- - - - 27030 uint
R
[`Su;g]
[ Su.g]
Logic (1 to 24)
Value Source G
View the value of Source 
G.
[`off] Off (62)
[``on] On (63)
9400
[offset 80]
0x7F 
(127)
1 to 24
0x1F (31)
- - - - 27031 uint
R
[`Su;h]
[ Su.h]
Logic (1 to 24)
Source Value H
View the value of Source 
H.
[`off] Off (62)
[``on] On (63)
9402
[offset 80]
0x7F 
(127)
1 to 24
0x20 (32)
- - - - 27032 uint
R
[``o;u]
[ o.v]
Logic (1 to 24)
Output Value
View the value of this 
function's output.
[`off] Off (62)
[``on] On (63)
9406
[offset 80]
0x7F 
(127)
1 to 24
0x22 (34)
- - - - 27034 uint
R
No Dis-
play
Logic (1 to 24)
Error
Read reported cause for 
logic error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
9410
[offset 80]
0x7F 
(127)
1 to 24
0x24 (36)
- - - - 27036 uint
R
[MAt]
[oPEr]
Math Menu
[`Su;A]
[ Su.A]
Math (1 to 24)
Source Value A
View the value of Source 
A.
-1,999.000 to 9,999.000°F 
or units
-1,128.000 to 5,537.000°C
6570
[offset 70]
0x7D 
(125)
1 to 24
0x10 (16)
- - - - 25016 float
RWES
[`Su;b]
[ Su.b]
Math (1 to 24)
Source Value B
View the value of Source 
B.
-1,999.000 to 9,999.000°F 
or units
-1,128.000 to 5,537.000°C
6572
[offset 70]
0x7D 
(125)
1 to 24
0x11 (17)
- - - - 25017 float
RWES
[`Su;C]
[ Su.C]
Math (1 to 24)
Source Value C
View the value of Source 
C.
-1,999.000 to 9,999.000°F 
or units
-1,128.000 to 5,537.000°C
6574
[offset 70]
0x7D 
(125)
1 to 24
0x12 (18)
- - - - 25018 float
RWES
Note: Some values will be rounded off to fit in the four-character display. Full values 
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read 
W: Write 
E: EEPROM 
S: User Set