User guide
Watlow EZ-ZONE
®
 RMH Module  • 46 •  Chapter 3 Operations Page
  RM High Density Module  •  Operations Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& Read/
Write
No Dis-
play
Timer (1 to 24)
Error
Read reported cause for 
timer error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
13214
[offset 50]
0x83 
(131)
1 to 24
0x12 (18)
- - - - 31018 uint
R
[`Ctr]
[oPEr]
Counter Menu
[`Cnt]
[ Cnt]
Counter (1 to 24)
Count
View the function's total 
count.
0 to 9,999 12248
[offset 40]
0x82 
(130)
1 to 24
0xF (15)
217 30015 uint
R
[`Su;A]
[ Su.A]
Counter (1 to 24)
Source Value A
View the value of Source 
A.
[`off] Off (62)
[``on] On (63)
12232
[offset 40]
0x82 
(130)
1 to 24
7
- - - - 30007 uint
R
[`Su;b]
[ Su.b]
Counter (1 to 24)
Source Value B
View the value of Source 
B.
[`off] Off (62)
[``on] On (63)
12234
[offset 40]
0x82 
(130)
1 to 24
8
- - - - 30008 uint
R
[``o;u]
[ o.v]
Counter (1 to 24)
Output Value
View the value of this 
function's output.
[`off] Off (62)
[``on] On (63)
12238
[offset 40]
0x82 
(130)
1 to 24
0xA (10)
- - - - 30010 uint
R
No Dis-
play
Counter (1 to 24)
Error
Read reported cause for 
counter error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
12250
[offset 40]
0x82 
(130)
1 to 24
0x10 (16)
- - - - 30016 uint
R
[`LgC]
[oPEr]
Logic Menu
[`Su;A]
[ Su.A]
Logic (1 to 24)
Source Value A
View the value of Source 
A.
[`off] Off (62)
[``on] On (63)
9388
[offset 80]
0x7F 
(127)
1 to 24
0x19 (25)
- - - - 27025 uint
R
[`Su;b]
[ Su.b]
Logic (1 to 24)
Source Value B
View the value of Source 
B.
[`off] Off (62)
[``on] On (63)
9390
[offset 80]
0x7F 
(127)
1 to 24
0x1A (26)
- - - - 27026 uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values 
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read 
W: Write 
E: EEPROM 
S: User Set