User guide
Watlow EZ-ZONE
®
 RMH Module  • 43 •  Chapter 3 Operations Page
  RM High Density Module  •  Operations Page
Display
Parameter Name
Description
Range Default
Modbus 
Relative 
Address
CIP
Class 
Instance
Attribute
hex (dec)
Probus 
Index
Parameter
ID
Data 
Type 
& Read/
Write
[`o;SP]
[ o.SP]
Control Loop (1 to 16)
Open Loop Set Point
Set a fixed level of output 
power when in manual 
(open-loop) mode.
-100.0 to 100.0% 0.0 5222 
[offset 80]
0x6B 
(107)
1 to16
2
41 7002 float
RWES
[ALM]
[oPEr]
Alarm Menu
[`A;Lo]
[ A.Lo]
Alarm (1 to 24)
Low Set Point
If Alarm Type (Setup 
Page, Alarm Menu) is 
set to: 
process - set the process 
value that will trigger a 
low alarm.
deviation - set the span of 
units from the closed loop 
set point that will trigger 
a low alarm. A negative 
set point represents a 
value below closed loop 
set point. A positive set 
point represents a value 
above closed loop set 
point.
-1,999.000 to 9,999.000°F 
or units
-1,128.000 to 5,537.000°C
32.0 °F 
or 
units
0.0°C
2662
[offset 60]
0x6D 
(109)
1 to 24
2
18 9002 float
RWES
[`A;hi]
[ A.hi]
Alarm (1 to 24) 
High Set Point 
If Alarm Type (Setup 
Page, Alarm Menu) is 
set to: 
process - set the process 
value that will trigger a 
high alarm.
deviation - set the span of 
units from the closed loop 
set point that will trigger 
a high alarm.
-1,999.000 to 9,999.000°F 
or units
-1,128.000 to 5,537.000°C
300.0°F 
or 
units
150.0°C
2660
[offset 60]
0x6D 
(109)
1 to 24
1
19 9001 float
RWES
[A;Clr]
[ A.hi]
Alarm (1 to 24) 
Clear Request
User interface (RUI) ac-
cess to clear an alarm
Clear 
Ignore
Ignore - - - - - - - - - - - - - - - -
- - - -
[A;sir]
[A.Sir]
Alarm (1 to 24) 
Silence Request
User interface (RUI) ac-
cess to silence an alarm
Ignore
Silence
Ignore - - - - - - - - - - - - - - - -
- - - -
[`A;st]
[ A.St]
Alarm (1 to 24) 
State
View state of alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
Startup 2676
[offset 60]
0x6D 
(109)
1 to 24
9
- - - - 9009 uint
R
No Dis-
play
Alarm (1 to 24) 
Latched
Read this register to de-
termine if the alarm is 
latched
No (59)
Yes (106)
No 2678
[offset 60]
0x6D 
(109)
1 to 24
0x0A (10)
- - - - 9010
uint
R
Note: Some values will be rounded off to fit in the four-character display. Full values 
can be read with other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read 
W: Write 
E: EEPROM 
S: User Set