User guide
Watlow EZ-ZONE
®
 RMH Module  • 35 •  Chapter 2 Menu Conventions
Conventions Used in the Menu Pages
To better understand the menu pages that follow 
review the naming conventions used. When encoun-
tered throughout this document, the word "default" 
implies as shipped from the factory. Each page (Op-
erations, Setup and Factory) and their associated 
menus have identical headers defined below:
Header Name Definition
Display
Visually displayed infor-
mation from the control.
Parameter Name
Describes the function of 
the given parameter.
Range
Defines options available 
for this prompt, i.e., min/
max values (numerical), 
yes/no, etc... (further ex-
planation below).
Default
Values as delivered from 
the factory.
Modbus Relative Ad-
dress
Identifies unique param-
eters using either the 
Modbus RTU or Modbus 
TCP protocols (further ex-
planation below).
CIP (Common Indus-
trial Protocol)
Identifies unique param-
eters using either the De-
viceNet or EtherNet/IP 
protocol (further explana-
tion below).
Profibus Index
Identifies unique param-
eters using Profibus DP 
protocol (further explana-
tion below).
Parameter ID
Identifies unique param-
eters used with other soft-
ware such as, LabVIEW.
Data Type R/W
uint  = Unsigned 16 bit 
   integer
dint  = long, 32-bit
string  = ASCII (8 bits 
    per character)
float  = IEEE 754 32-bit
RWES =  Readable
 Writable
 EEPROM (saved)
   User Set (saved)
Remote User interface (RUI) Display
Visual information from the control is displayed to 
the observer using a fairly standard 7 segment dis-
play. Due to the use of this technology, several char-
acters displayed need some interpretation, see the 
list below:
[1] = 1 [0] = 0 [i] = i [r] = r
[2] = 2 [a] = A [j ] = J [S] = S
[3] = 3 [b] = b [H] = K [t] = t
[4] = 4 [c] , [C] = c [l] = L [U] = u
[5] = 5 [d] = d [m ] = M [u] = v
[6] = 6 [e] = E [n] = n [w ] = W
[7] = 7 [f] = F [o] = o [y ] = y
[8] = 8 [g] = g [p] = P [2] = Z
[9] = 9 [h] = h [q ] = q
Note:
The RUI is optional equipment.
Range
Within this column notice that on occasion there will 
be numbers found within parenthesis. This number 
represents the enumerated value for that particular 
selection. Range selections can be made simply by 
writing the enumerated value of choice using any of 
the available communications protocols. As an ex-
ample, turn to the Setup Page and look at the Analog 
Input [`Ai] menu and then the Sensor Type [Sen] 
prompt. To turn the sensor off simply write the value 
of 62 (off) to Modbus register 388 and send that value 
to the control.
Communication Protocols and Software Tools
All RM modules come with Watlow's Standard 
Bus protocol. This protocol is used primarily for 
inter-module communications but is also used with 
SpecView by Watlow, LabVIEW and EZ-ZONE Con-
figurator software (free download from Watlow's web 
site (http://www.watlow.com). Along with Standard 
Bus, the RMH module can also be ordered with Mod-
bus RTU (only one protocol can be active at any given 
time). The RMA (Access) module has options for sev-
eral different protocols listed below:
- Modbus RTU 232/485
- EtherNet/IP, Modbus TCP
- DeviceNet
- Profibus DP
Modbus RTU Protocol
All Modbus registers are 16-bits and as displayed 
in this manual are relative addresses (actual). Some 
legacy software packages limit available Modbus reg-
isters to 40001 to 49999 (5 digits). Many applications 
today require access to all available Modbus registers 
which range from 400001 to 465535 (6 digits). Wat-
low EZ-ZONE controllers support 6 digit Modbus reg-
isters. For parameters listed as float notice that only 
one (low order) of the two registers is listed, this is 
true throughout this document. By default the low or-
der word contains the two low bytes of the 32-bit pa-
rameter. As an example, look in the Operations Page 
for the Process Value. Find the column identified in 










