User guide
Warning: ç
Use National Electric (NEC) or other 
country-specific standard wiring and 
safety practices when wiring and 
connecting this controller to a power 
source and to electrical sensors or pe-
ripheral devices. Failure to do so may 
result in damage to equipment and 
property, and/or injury or loss of life.
Note:
Maximum wire size termination and 
torque rating: 
• 0.0507 to 3.30 mm
2
 (30 to 12 AWG) 
  single-wire termination or two 1.31 
 mm
2
 (16 AWG) 
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be labeled 
differently, depending on the model
number.
Note:
To prevent damage to the controller, 
do not connect wires to unused ter-
minals.
Note:
Maintain electrical isolation between 
digital input-outputs, switched dc/open 
collector outputs and process outputs 
to prevent ground loops.
Warning: ç
Explosion Hazard – Substitution of 
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect 
while the circuit is live or unless the 
area is known to be free of ignitable 
concentrations of flammable sub-
stances.
Watlow EZ-ZONE
®
 RMH Module  • 32 •  Chapter 2 Install and Wire 
Note:
When connecting the USB converter to the PC it is suggested that the La-
tency Timer be changed from the default of 16 msec to 1 msec. Failure to 
make this change may cause communication loss between the PC running 
ZE-ZONE Configurator software and the control.
To modify Latency Timer settings follow the steps below:
1. Navigate to Device Manager.
2. Double click on Ports.
3. Right click on the USB serial port in use and select Properties.
4. Click the tab labeled Port settings and then click the Advance button.