User guide
Warning: ç
Use National Electric (NEC) or other 
country-specific standard wiring and 
safety practices when wiring and 
connecting this controller to a power 
source and to electrical sensors or pe-
ripheral devices. Failure to do so may 
result in damage to equipment and 
property, and/or injury or loss of life.
Note:
Maximum wire size termination and 
torque rating: 
• 0.0507 to 3.30 mm
2
 (30 to 12 AWG) 
  single-wire termination or two 1.31 
 mm
2
 (16 AWG) 
• 0.8 Nm (7.0 in-lb.) torque
Note:
Adjacent terminals may be labeled 
differently, depending on the model
number.
Note:
To prevent damage to the controller, 
do not connect wires to unused ter-
minals.
Note:
Maintain electrical isolation between 
digital input-outputs, switched dc/open 
collector outputs and process outputs 
to prevent ground loops.
Warning: ç
Explosion Hazard – Substitution of 
component may impair suitability for
CLASS I, DIVISION 2.
Warning: ç
Explosion Hazard - Do not disconnect 
while the circuit is live or unless the 
area is known to be free of ignitable 
concentrations of flammable sub-
stances.
Watlow EZ-ZONE
®
 RMH Module  • 28 •  Chapter 2 Install and Wire 
Open Collector Wiring Example Using DO 1-12
VDC
Collector Outputs
Internal Circuitry
Power Supply
5 to 32 VDC
Relay
+
-
Common
Internal Supply
Diode
Fuse
An example fuse is 
Bussmann 
AGC-1 1/2
B_
Z_
D_
D_
D_
D_
D_
D_
As an open collector output (see graphic below), use an external power sup-
ply with the negative wired to B_, the positive to the coil of a pilot mechani-
cal relay and the other side of the coil wired to the output of choice (D_). 
Each open collector output can sink 1.5 A with the total for all open collector 
outputs not exceeding 8 amperes. Ensure that a kickback diode is reversed 
wired across the relay coil to prevent damage to the internal transistor.
Output 1 - 4 and 7 - 10 Mechanical Relay, Form A
  RMH Part # Digit 7, 8 is J
normally open
common
L1
K1
L2
K2
L3
K3
L4
K4
Slot D
normally open
common
normally open
common
normally open
common
normally open
common
L7
K7
L8
K8
L9
K9
L10
K10
Slot E
normally open
common
normally open
common
normally open
common
•  5 A at 240VÅ (ac) or 30VÎ 
(dc) maximum resistive 
load
•  20 mA at 24V minimum 
load
•  125 VA pilot duty @ 
120/240VÅ (ac), 25 VA at 
24VÅ (ac)
•  100,000 cycles at rated load
•  Output does not supply 
power.
•  for use with ac or dc
See Quencharc note.
-  Slot D Outputs 1 - 6 
 RMHx-xx(J)x-xxxx
  - Slot E Outputs 7 - 10
 RMHx-xxx(J)-xxxx
Mechanical Relay Form A
L_
K
_
Internal Circuitry