User guide

Watlow EZ-ZONE
®
RMH Module 151 Appendix
Input Type
Max
Error
@ 25
Deg C
Accuracy
Range
Low
Accuracy
Range
High
Units
mA ac ±5 0 50
mAmps
AC
Potentiometer,
1K range
±1 0 1000 Ohms
Operating Range
Input Type Range Low Range High Units
J -210 1200 DegC
K -270 1371 DegC
T -270 400 DegC
N -270 1300 DegC
E -270 1000 DegC
R -50 1767 DegC
S -50 1767 DegC
B -50 1816 DegC
C 0 2315 DegC
D 0 2315 DegC
F (PTII) 0 1343 DegC
RTD (100
ohm)
-200 800 DegC
RTD (1000
ohm)
-200 800 DegC
mV 0 50 mV
Volts 0 10 Volts
mAdc
0 20
mAmps
DC
mAac
0 50
mAmps
AC
Resistance, 5K
range
0 5000 Ohms
Resistance,
10K range
0 10000 Ohms
Resistance,
20K range
0 20000 Ohms
Resistance,
40K range
0 40000 Ohms
Resistance,
40K range
0 40000 Ohms
Potentiometer,
1K range
0 1200 Ohms
Thermistor Input
Input
Type
Max Error
@ 25 Deg C
Accuracy
Range
Low
Accuracy
Range
High
Units
Thermis-
tor, 5K
range
±5 0 5000 Ohms
Thermis-
tor, 10K
range
±10 0 10000 Ohms
Thermistor Input (cont.)
Input
Type
Max Error
@ 25 Deg C
Accuracy
Range
Low
Accuracy
Range
High
Units
Thermis-
tor, 20K
range
±20 0 20000 Ohms
Thermis-
tor, 40K
range
±40 0 40000 Ohms
0 to 40KΩ, 0 to 20KΩ, 0 to 10KΩ, 0 to 5KΩ
2.252KΩ and 10KΩ base at 25°C
Linearization curves built in
Third party Thermistor compatibility requirements
Base R
@ 25C
Alpha
Techniques
Beta
THERM
YSI
Thermistor
Curve
2.252K Curve A 2.2K3A 004 A
10K Curve A 10K3A 016 B
10K Curve C 10K4A 006 C
Digital Input
Update rate 10Hz
DC voltage
- Max. input 36V at 3mA
- Min. high state 3V at 0.25mA
- Max. low state 2V
Dry Contact
Update rate 10Hz
Min. open resistance 10KΩ
Max. closed resistance 50Ω
Output Hardware
Electromechanical relay, Form A, 5A, 24 to 240VÅ (ac) or 30VÎ
(dc) max., resistive load, 100,000 cycles at rated load. Requires
a min. load of 20mA at 24V, 120/240 VÅ (ac) 125VA, 24VÅ (ac)
25VA pilot duty
Digital outputs
- Update rate 10Hz
- Switched DC
- Output voltage 20VÎ (dc)
- Max. supply current source 40mA at 20VÎ (dc) and 80mA at
12VÎ (dc)
- Open Collector
- Switched voltage max.: 32VÎ (dc)
- Max. switched current per output: 1.5A
- Max. switched current for all 6 outputs combined: 8A
Process/Retransmit Outputs, Range Selectable
- 0 to 10V Î(dc) into a min. 4KΩ load
- 0 to 20mA into max. 400Ω load
Resolution
- dc ranges: 0.2mV nominal
- mA ranges: 0.4µA nominal
Calibration Accuracy
- dc ranges: ±15 mV
- mA ranges: ±30 µA
Temperature Stability
- 100 ppm FSR/°C
Quad Solid-State Relays
2A at 20 to 264VÅ (ac) maximum resistive load
• 50 VA 120/240VÅ (ac) pilot duty
Programmable Application Blocks
Actions (events) 24 total
Alarms 24 total