Indication Description Possible Cause(s) Corrective Action
RUI value to high
[ual;h] 
Value to high to be displayed 
in 4 digit LED display 
>9999
• Incorrect setup • Check scaling of source data
Detection of and Rules Around Abnormal Sensor Conditions 
Inputs Detection of Abnormal Conditions
Thermocouple
Shorted No direct detection, Open loop firmware detection.
Open Yes, Parasitic pull-up
Reversed Yes, firmware detection
Current Source
Shorted  Range limiting only
Open  Range limiting only
Reversed  Range limiting only
Voltage Source
Open Range limiting only
Shorted  Range limiting only
Reversed  Range limiting only
RTD
S1 open  Yes, pulled up.
S2 open  Not implemented.
S3 open  Yes, pulled up.
S1 short to S2  Yes, pulled up
S1 short to S3   Yes, pulled down to under range.
S2 shorted to S3  Not implemented, Possible, monitor S2 voltage.
S1 and S2 open  Yes, pulled down to under range.
S1 and S3 open  Yes, S1 pulled up.
S2 and S3 open  Yes pulled up.
Thermistor
S1 open  Yes, pulled up to sensor over range.
S3 open  Yes, pulled up to sensor over range.
S1 short to S3  Yes, pulled down to sensor under range.
S1 and S3 open  Yes, S1 pulled up to sensor over range.